Permit Information
Permit NumberFIR10-00425
StatusFinaled
Name TRIBAL FIRE SYSTEMS
Site Address 2481 E WARM SPRINGS AVE
Project NameWarm Springs Golf Maint Bldg
Customer Number 
ePlanReviewNo
Description
The Fire Sprinkler Scope of work consists of a long narrow prefabricate maintenance facility with Z purlin and beam construction. The west portion has a small office area. The sprinkler system is designed for ordinary hazard II. The layout is a side feed system with a 4” main and telescoping branch piping. The system is supplied by 6” C-900 underground piping and a 4” backflow preventer.

Plan Mod Scope:
? Changed the underground slightly
? Added and additional branch line due to construction change. New hydraulics were provided.
? Added a sprinkler below an overhead door. Orignal plans called fore a roll up door.
? Revised the earthquake bracing due to construction.

Building Department Scope:

Boise City Parks - Warm Springs Golf Course - Storage and Office Building - To construct a new 7,105 square foot, one story, pre-engineered metal office, shop and storage building. This permit also includes related site improvements. This building is fully fire sprinkled. (Office: 910 sq. ft., Shop: 1730 sq. ft., Storage: 4465 sq. ft.) All construction per the approved plans and attached comment list. JCM


Notice for Fire Protection Contractor:

The building permit has not been issued at this time. The building department may determine that changes are required to the building plans in order to meet code. These changes may affect the sprinkler system. The sprinkler contractor will be required to make all necessary changes that may be required. Therefore, if the sprinkler contractor chooses to proceed without an issued building permit they will do so on their own cognizance
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/20/20111/20/20111/20/2011APASS
DetailsForrest France
Correction items verified for completion. Fire sprinkler permit finaled.
INSP-Final Inspection1/18/20111/19/20111/19/2011ACANC
DetailsForrest France
I''m coming from Kuna please give me atleast a 30 minute heads up. Thx, Clarence Phone #: ###-#### >> Inspection requested via web by Clarence McLain Inspection cancelled from web by: John Venche
INSP-Sprinkler Rough-in/Hydro1/13/20111/14/20111/14/2011APART
DetailsTroy Cobbley
Overhead hydrostatic test completed satisfactory per inspector 410.
INSP-Sprinkler Rough-in/Hydro1/12/20111/13/20111/13/2011PPART
DetailsForrest France
Underground fire supply line hydrostatic test completed acceptable.
INSP-Final Inspection1/12/20111/13/20111/13/2011PNR
DetailsForrest France
Missing field ceiling tile, escutcheons, DCVA certification, forward flow, etc.
INSP-Sprinkler Rough-in12/27/201012/28/201012/28/2010APART
DetailsForrest France
Overhead rough-in approved for cover at the office area grid ceilings. Need to provide coverage below the 6'x6' hood at the shop bay, include seismic clearance at main penetrations through non-frangible wall construction, install correct temp. rated heads within the zone of influence at unit heaters in the shop areas (SW and uprights).
INSP-Sprinkler Rough-in12/16/201012/17/201012/17/2010ADEFR
DetailsForrest France
Inspection postponed due to jobsite condtions and access to city approved plan set on site.
INSP-Supply line flush12/1/201012/2/201012/6/2010PPART
DetailsForrest France
Underground fire supply line flush completed acceptable.
INSP-Supply line flush11/30/201012/1/201012/1/2010PCANC
DetailsForrest France
Phone #: ###-#### >> Inspection requested via web by John Venche Inspection cancelled from web by: John Venche
INSP-Sprinkler Rough-in/Hydro10/12/201010/13/201010/13/2010PFAIL
DetailsForrest France
UG fire supply line hydrostatic test failed due to pressure loss below 200 psi at the guage.
INSP-Sprinkler Rough-in/Hydro10/13/201010/13/201010/13/2010APART
DetailsForrest France
Underground fire supply line is approved for bury. Need to provide method for seismic clearance at the floor slab. Discussed fire code review notes regarding PI valves and riser room ratings.