Information based on query as of Thursday, July 4, 2024.
Permit Information
Permit NumberFIR10-00429
StatusFinaled
Name SIMPLEX GRINNELL
Site Address 1000 N CURTIS RD
Project NameSARMC ELEVATOR RECALL
Customer Number 
ePlanReviewNo
Description
9/6/2012 PLAN MODIFICATION (no initiating devices affected): This plan modification is to provide non-addressable relay modules to control the recall functions of the elevator, and to tie in the elevator fire curtains to close on general alarm. 9/3/2010:This quick permit is to provide a heat and a smoke detector in the elevator equipment room for elevator recall and shunt trip functions. Devices are to be added to the existing circuit. There is no indication of the fireman's hatlight on the I/O matrix. Per the contractor, the elvators do not contain a fireman's hat light. If the elevator has a fireman's hat light, a plan modification shall be required to include these functions. There are no written review comments. There is no associated building permit.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/15/20131/16/20131/16/2013APASS
DetailsTroy Cobbley
Permit finaled
FIR-Aging Inspection1/9/20131/9/20131/15/2013 NR
DetailsTroy Cobbley
FIR-Aging Inspection9/28/20129/28/201210/1/2012 NR
DetailsTroy Cobbley
Forwarded information to Scott for further action.
FIR-Aging Inspection4/30/20124/30/20125/2/2012 NR
DetailsTroy Cobbley
I spoke to Charlie and he is going to follow up on status.
FIR-Aging Inspection1/20/20121/20/20121/23/2012 NR
DetailsTroy Cobbley
I met with Tamara and Charlie and discussed the project status. The projects will be followed up on and their status relayed to me.
INSP-Conference5/5/20115/5/20115/5/2011PDONE
DetailsTroy Cobbley
I spoke to Tammy with SimplexGrinnell about getting work completed and the inspection finaled. She is following up and will contact me with the project status.
FIR-Aging Inspection3/22/20113/22/20113/29/2011 NR
DetailsTroy Cobbley
Per Brian with SImplex Charlie is working on getting the elevators done.
FIR-Aging Inspection12/15/201012/15/201012/16/2010 NR
DetailsTroy Cobbley
Per Charlie this permit is on their list of permits to get inspected.
INSP-Final Inspection10/15/201010/15/201010/15/2010PFAIL
DetailsTroy Cobbley
No test was performed at this location. Plan modifications are needed since a hat/light does light up in the elevator car. Also no shunt trip has been provided for the heat detector to activate. There are also sprinkler heads at the top and bottom of the elevator shaft.