Permit Information
Permit NumberFIR10-00483
StatusFinaled
Name RCI ELECTRICAL SOLUTIONS
Site Address 877 W FRONT ST
Project NameTHE ASPEN-TURNER R.E.G. TI
Customer Number 
ePlanReviewNo
Description
This quick permit is to relocate a strobe only and add two new speaker/strobes to the existing fire alarm system to accomodate a tenant improvement. Approval is subject to field measurement of the EOL voltage drop. For appliances with an operating voltage range of 16V – 33V, the minimum acceptable voltage is 19.6V with the AC power off. Any measurement below this voltage will be considered insufficient to run the NACs at the end of useful battery life of 20.4V. UL 864, Standard for Control Units for Fire Signaling Systems.The installing contractor shall have available at final inspection a voltage meter and measure end of line voltages; witnessed by the field inspector. A building map shall be posted at the FACP indicating the type and location of all alarm initiating devices, by device address or zone number. Provide updated map reflecting the floor plan and all initiating device locations. 2007 NFPA 72 4.4.6.1. There are no written review comments. Associated building permit: BLD10-01322 (TURNER REAL ESTATE GROUP - 1ST STORY - THE ASPEN BUILDING) This building is fire sprinklered because it is a high rise. To prepare an existing 1,102 square foot shell space located on the 1st story of the Aspen Building for occupancy as a real estate office. Work is to include interior nonbearing walls, suspended acoustical ceilings, ceiling shelf, millwork, and finishes. The restroom was installed under the shell permit and is required to be fully accessible to the disabled. The work is required to comply with the approved drawings, with the plan review report, and with all applicable codes and ordinances. The fire sprinkler system is required to comply with NFPA 13 as regulated by the Fire Department. **CJW**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/13/201010/14/201010/14/2010APASS
DetailsForrest France
Fire alarm work completed satisfactory, functional testing passed. Permit finaled.
INSP-Final Inspection10/12/201010/13/201010/13/2010PCANC
DetailsForrest France
barry Phone #: ###-#### Inspection cancelled from web by: BARRY KENDALL