Permit Information
Permit NumberFIR10-00490
StatusFinaled
Name NORTHWEST SALES COMPANY
Site Address 703 S AMERICANA BLVD Unit: 120
Project NameST. LUKE’S ORTHOPEDIC- AMERICA
Customer Number 
ePlanReviewNo
Description
11/16/10 PLAN MODIFICATION (12 initiating devices affected):
This plan modification is to relocate an existing pull station, add pull stations at new exits, and extend the existing corridor automatic smoke detection into the new areas. In addition, this plan modification is to incorporate previous review comments and field modifications.

10/11/10: This fire alarm permit is to provide notification and a duct detector for HVAC shutdown/monitoring due to a tenant improvement. New duct detector to be connected to the existing FACP. A new NAC panel is being provided for the new notification devices.

Associated building permit: BLD10-01201 (ST. LUKE'S Orthopedic Clinic - American West Bldg - Ste # 120) Permit is to remodel an existing 6,300 square foot portion of an existing building. The 6,300 square feet is a combination of the area left over after BLD10-01138 and Pioneer Title & Escrow (BLD05-03033). Approval contingent upon adhering to the approved plans on file. Work to include: [construction of interior non-bearing walls to create separate sex accessible bathrooms, two unisex accessible bathrooms, 12 exam rooms, 4 offices, a reception / waiting area, a new vestibule, 5 storage rooms, a nurses station, and a wet clean room], installation of new plumbing, installation of new lighting, installation of new mechanical, installation of new doors / hardware, and finishes in compliance with chapter 8 of the 2006 IBC. This building is fully fire sprinklered any alterations or modifications to the sprinkler system WILL REQUIRE A SEPARATE PERMIT and shall be installed per NFPA #13 as regulated by the fire department. Racking that exceeds 8 ft. in height requires a separate Building Permit be submitted and approved before installation. **TLW**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection12/13/201012/14/201012/14/2010APASS
DetailsForrest France
Noted corrections finished, fire alarm work passed functional testing. Permit finaled.
INSP-Final Inspection12/9/201012/10/201012/10/2010AFAIL
DetailsTroy Cobbley
See the city approved plans for the locations of the deficiencies. They include adding a/v coverage in Offices 105 and 106, providing coverage at the end of a corridor where an existing a/v had been removed, relocating a smoke detector located too close to a supply air diffuser, and setting the correct candella for a strobe in the Vontrol Room on the existing side of this building. No devices were tested. Per plan review as-builts can be provided for the changes.
INSP-Conference12/9/201012/9/201012/9/2010PDONE
DetailsForrest France
Regarding sync issues at notification zones per NFPA 72 6.8.5.3.