Permit NumberFIR10-00494
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 12000 W EXECUTIVE DR
Project NameScentsy at EDOP
Customer Number 
ePlanReviewNo
Description
The Fire Sprinkler Scope of work consists of changing portions of two existing systems to group A plastic storage on racks. The storage is Styrofoam packing material. Storage is 25’ high and the maximum building height is 32’. There are no solid shelves. Aisle widths shall be 3.5’ or greater. The existing control mode sprinklers are being changed to ESFR sprinklers. A new fire pump is being provided rated at 1250 Gpm @ 80 Psi. A draft curtain is shown separating the control mode sprinklers from the ESFR sprinklers.


Building Department Scope:

(Shell & Core – Fire Pump Room) Permit is to upgrade an existing fire riser room to be fully rated and comply with the other provisions of a Fire Pump Room (Last occupied by BMC West Door Plant). Approval contingent upon adhering to the approved plans on file. Work to include: construction of interior non-bearing walls to create the rated fire pump room, installation of new accessible door / hardware, installation of new mechanical vents, and finishes in compliance with chapter 8 of the 2006 IBC. This building is fully Fire Sprinklered with an approved Fire Alarm system. Any alterations or modifications to the buildings Fire Sprinkler or Fire Alarm system WILL REQUIRE A SEPARATE PERMIT and shall be installed per NFPA 13 & NFPA 72 as regulated by the Boise Fire Department. Any racking installed exceeding 8 ft. in height will require a separate racking permit. **TLW**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection3/28/20113/28/20113/28/2011PPASS
DetailsTroy Cobbley
permit finaled
INSP-Final Inspection2/16/20112/16/20112/16/2011PCANC
DetailsTroy Cobbley
I spoke to Jeff on the phone about the remaining items which are test papers, ventilation and emergency lighting in the pump room.
INSP-Sprinkler Rough-in/Hydro2/9/20112/9/20112/9/2011PPASS
DetailsTroy Cobbley
Hydro test passed. The 12 missing uprights have been added and the additional upright in the fire pump room has been provided. These items can be removed from the previous correction notice.
INSP-Final Inspection2/4/20112/7/20112/7/2011PCANC
DetailsTroy Cobbley
Permit is not ready for final. See "rough-in" inspection notes.
INSP-Sprinkler Rough-in/Hydro2/4/20112/7/20112/7/2011PFAIL
DetailsTroy Cobbley
See the city approved plans/notes for items marked. They include pump room ventilation, pump room emergency lighting, additional sprinkler coverage in the pump room and 12 missing ESFR heads near the pump room and a hydro test.
INSP-Conference1/8/20111/11/20111/12/2011PPASS
DetailsTroy Cobbley
Certification of the fire pump passed. No other items inspected at this time.