Permit Information
Permit NumberFIR10-00521
StatusFinaled
Name SIMPLEX GRINNELL
Site Address 1055 N CURTIS RD
Project NameSARMC BMAC ELEVATOR RECALL
Customer Number 
ePlanReviewNo
Description
This quick permit is to provide elevator recall functions for elevator #1 & #2. Per the contractor, this building is not sprinklered, and there are no fireman's hat light functions available. Seven smoke detectors and four control zams are being added to the existing fire alarm system. There is no associated building permit.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/15/20131/16/20131/16/2013APASS
DetailsTroy Cobbley
Permit finaled
FIR-Aging Inspection1/14/20131/14/20131/15/2013 NR
DetailsTroy Cobbley
FIR-Aging Inspection9/24/20129/24/201210/1/2012 NR
DetailsTroy Cobbley
Forwarded information to Scott for further action.
FIR-Aging Inspection4/26/20124/26/20125/2/2012 NR
DetailsTroy Cobbley
Charlie is going to schedule Dante to finishs the as-builts.
FIR-Aging Inspection1/20/20121/20/20121/23/2012 NR
DetailsTroy Cobbley
I met with Tamara and Charlie and discussed the project status. The projects will be followed up on and their status relayed to me.
FIR-Aging Inspection4/27/20114/27/20115/5/2011 NR
DetailsTroy Cobbley
I spoke to Tammy with SimplexGrinnell about getting work completed and the inspection finaled. She is following up and will contact me with the project status.
INSP-Final Inspection2/10/20112/16/20112/16/2011AFAIL
DetailsTroy Cobbley
Provide signage at the inoperative firemans controls in both elevators as discussed or make all functions operational.
INSP-Final Inspection1/28/20112/9/20112/9/2011ACANC
DetailsTroy Cobbley
The contractor did not have the city approved job site copy plans on site. No inspection was performed.