Permit Information
Permit NumberFIR10-00541
StatusFinaled
Name SIMPLEX GRINNELL
Site Address 6094 W EMERALD ST
Project NameSt. Al's RMC
Customer Number 
ePlanReviewNo
Description
This quick permit is to provide a new strobe and relocate an existing pull station to accomodate a tenant improvement. Approval is subject to field measurement of the EOL voltage drop. For appliances with an operating voltage range of 16V – 33V, the minimum acceptable voltage is 19.6V with the AC power off. Any measurement below this voltage will be considered insufficient to run the NACs at the end of useful battery life of 20.4V. UL 864, Standard for Control Units for Fire Signaling Systems. The installing contractor shall have available at final inspection a voltage meter and measure end of line voltages; witnessed by the field inspector. There are no written review comments. Associated building permit: BLD10-01693 (FAMILY MEDICINE RESIDENCY OF IDAHO - St. Al's RMC) Permit is to remodel an existing 8,019 square foot medical office building in order to install a pharmacy and perform other minor remodeling work. Approval contingent upon adhering to the approved plans on file. Work to include: [construction of interior non-bearing walls to create a records room, to create an office, to enlarge an exam room, to create a pharmacy, and to enlarge a small office to encompass two existing smaller offices], installation of new accessible service counters, and finishes in compliance with chapter 8 of the 2006 IBC. This building is not fire sprinklered. Racking that exceeds 8 ft. in height requires a separate Building Permit be submitted and approved before installation. **TLW**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection6/21/20116/22/20116/22/2011APASS
DetailsForrest France
Fire alarm permit finaled.
INSP-Final Inspection6/20/20116/21/20116/21/2011APASS
DetailsForrest France
Modification tested okay, as-builts recieved. Inspection passed.
FIR-Aging Inspection4/27/20114/27/20115/5/2011 NR
DetailsTroy Cobbley
I spoke to Tammy with SimplexGrinnell about getting work completed and the inspection finaled. She is following up and will contact me with the project status.
INSP-Final Inspection2/24/20112/25/20112/25/2011PFAIL
DetailsTroy Cobbley
No testing was actually performed. The pull station is required to be relocated as per the approved plans. Not addressed on the plans was the requriement for audibility in the new open office and in the pharmacy. A visual device is required in the new restroom that is located within the pharmacy. Also in the reception area at the pharmacy has what appears to be an existing strobe mounted in a new wall. This device will have to meet current code for spacing or the code under which is was installed if it had not been modified.