Permit Number | FIR10-00541 |
Status | Finaled |
Name |
SIMPLEX GRINNELL
|
Site Address |
6094 W EMERALD ST
|
Project Name | St. Al's RMC |
Customer Number | |
ePlanReview | No |
Description |
This quick permit is to provide a new strobe and relocate an existing pull station to accomodate a tenant improvement. Approval is subject to field measurement of the EOL voltage drop. For appliances with an operating voltage range of 16V – 33V, the minimum acceptable voltage is 19.6V with the AC power off. Any measurement below this voltage will be considered insufficient to run the NACs at the end of useful battery life of 20.4V. UL 864, Standard for Control Units for Fire Signaling Systems. The installing contractor shall have available at final inspection a voltage meter and measure end of line voltages; witnessed by the field inspector. There are no written review comments. Associated building permit: BLD10-01693 (FAMILY MEDICINE RESIDENCY OF IDAHO - St. Al's RMC) Permit is to remodel an existing 8,019 square foot medical office building in order to install a pharmacy and perform other minor remodeling work. Approval contingent upon adhering to the approved plans on file. Work to include: [construction of interior non-bearing walls to create a records room, to create an office, to enlarge an exam room, to create a pharmacy, and to enlarge a small office to encompass two existing smaller offices], installation of new accessible service counters, and finishes in compliance with chapter 8 of the 2006 IBC. This building is not fire sprinklered. Racking that exceeds 8 ft. in height requires a separate Building Permit be submitted and approved before installation. **TLW**
|