Permit NumberFIR10-00548
StatusFinaled
Name ALLIED GENERAL FIRE & SECURITY
Site Address 4714 W STATE ST
Project NameCOLLISTER SHOPPING CENTER
Customer Number 
ePlanReviewNo
Description
1/4/11 PLAN MODIFICATION (no initiating devices are affected): This plan modification is to increase the candela ratings of several notification devices to accommodate larger device spacing.

11/12/10: This fire alarm permit is to provide notification and connect to the existing fire alarm system to accommodate a tenant improvement.

Associated building permit: BLD10-02170 (GREEN CHUTES & SALT TEARS COFFEE SHOP) One-hr construction and fire sprinklers are used for building area increase. To remodel an existing 11,236 square foot tenant space (total of 11,566 square feet after a 330 square foot mezzanine is constructed) for a restaurant and retail sales tenant. No cooking operations that create grease laden vapors are allowed within this tenant space or under the canopy. The proposed BBQ is required to be located outside of this building in an area that is open to the sky. Work is to include two restrooms accessible to the disabled, interior nonbearing partitions, four 160 square foot shipping containers to function as rooms, ramps and landings to provide access to the shipping containers, millwork, interior finishes, dining tables and chairs, service counters, a Type II hood, and kitchen equipment. The shipping containers are to have the doors welded in the open position. Mezzanine work includes wood stud bearing walls, gypsum board shear walls, wood floor joists, and wood floor sheathing. The mezzanine floor and the supporting walls are required to be of 1-hr fire-resistance-rated construction. Mezzanine stairway work includes steel stringers, steel columns, steel beams, and steel treads. This building is required to be maintained as a Type V-A building (i.e. 1-hr fire-resistance-rated). Work includes removing the existing suspended 1-hr ceiling and creating a 1-hr fire-resistance-rated roof-ceiling assembly using a gypsum board membrane. The work is required to comply with the approved drawings, with the plan review report, and with all applicable codes and ordinances. The fire sprinkler system is required to be maintained in compliance with NFPA 13 as regulated by the Fire Department. **CJW**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/12/20111/13/20111/13/2011APASS
DetailsTroy Cobbley
permit finaled
INSP-Final Inspection1/7/20111/10/20111/10/2011AFAIL
DetailsTroy Cobbley
Todays test included testing of the flow switch, PIV and EOL voltage for the audio/visual devices in the new tenant space. Supervision of the new NAC panel by the new FACP was verified as well. Still need the duct smoke detector locations addressed/tested, correct descriptions at teh new remote annunciator and the correct documentation as per telephone conversations with the plan reviewer.
INSP-Final Inspection1/6/20111/7/20111/7/2011AFAIL
DetailsTroy Cobbley
Inspection was cancelled due to tenant complaints per Jeff's direction. I went ahead and verified locations of the audio/visuals. Everything was located ok except one 115cd ceiling mount will need to be increased to 135cd to provide adequate coverage to the "welding curtain" walls. These walls were not shown on the city approved plans. I also noted that the two new duct smoke detectors were not located per code. I discussed possible solutions with the on site fire alarm tech and the tenants designer. No actual testing of devices including the end of line voltage drops were done.
INSP-Final Inspection12/28/201012/30/201012/30/2010AFAIL
DetailsTroy Cobbley
Many of the strobes are overspaced. Visual coverage is required in the Janitors closet since it is now a part of the common area due to the door not being installed. The PIV valve label at the remote annunciator needs to be labeled correctly. It is currently labeled "anti-freeze". The notification circuit was not activated for testing due to the outstanding issues. A drawing plan modification will be required to be submitted for approval if additional devices are added or candella modified.
INSP-Final Inspection12/28/201012/29/201012/28/2010ACANC
DetailsTroy Cobbley
Call Jeff at ###-#### Phone #: ###-#### >> Inspection requested via web by Mike Brown Inspection cancelled from web by: Mike Brown