INSP-Final Inspection | 7/1/2011 | 7/5/2011 | 7/5/2011 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled.
|
INSP-Sprinkler Rough-in | 6/29/2011 | 6/30/2011 | 6/30/2011 | A | PASS |
Troy Cobbley
|
|
|
The last phase of the sprinkler piping can be covered. A final inspection can be called in when all of the ceiling tile has been installed.
|
INSP-Sprinkler Rough-in | 5/17/2011 | 5/17/2011 | 5/17/2011 | P | PASS |
Troy Cobbley
|
|
|
The piping in two additional exam rooms and one restroom is ok to cover. See the city approved plans for the locations marked in red.
|
INSP-Sprinkler Rough-in | 4/28/2011 | 4/29/2011 | 4/29/2011 | A | PART |
Troy Cobbley
|
|
|
Phase 3 and 5 are complete
|
INSP-Sprinkler Rough-in | 3/24/2011 | 3/25/2011 | 3/25/2011 | P | PART |
Forrest France
|
|
|
See approved plan set for area outlined in blue highlighter and initialed with today's date for locations approved for ceiling cover.
|
INSP-Final Inspection | 2/17/2011 | 2/17/2011 | 2/17/2011 | P | PART |
Troy Cobbley
|
|
|
See the city approved building plans for room locations marked "ok" where the sprinkler work is complete.
|
INSP-Sprinkler Rough-in | 2/8/2011 | 2/9/2011 | 2/9/2011 | A | PASS |
Troy Cobbley
|
|
|
See the city approved plans for locations where the sprinkler piping can be covered. It has been marked and initialed in red.
|
INSP-Final Inspection | 1/27/2011 | 1/28/2011 | 1/28/2011 | A | PART |
Tim Frost
|
|
|
Ok to cover Phase 1. Highlighted in yellow on the job site plans.
|
INSP-Final Inspection | 1/27/2011 | 1/27/2011 | 1/27/2011 | P | NR |
Tim Frost
|
|
|
Inspector unable to contact contractor to arrange for inspection. Inspector visited jobsite and no contractor was present. Inspection cancelled.
|