Permit Number | FIR10-00567 |
Status | Finaled |
Name |
FIRE SENTRY SYSTEMS
|
Site Address |
276 N 8TH ST
|
Project Name | IDAHO BLDG - 1ST FLR |
Customer Number | |
ePlanReview | No |
Description |
This quick permit is to monitor a new kitchen hood suppression system with an existing fire alarm panel. Any other modifications to the fire alarm system shall require a plan modification. The new hood connection is being added to an existing zone that has alarm initiating devices already on it. To comply with NFPA 72 and IFC requirements for the hood suppression system alarm signal to report/annunciate separately, the contractor is using a previously approved (for this project/building only) method (please see one-line diagrams). This is approved only with the understanding that the monitoring service must be notified of the hood suppression system activation regardless of the condition of that zone (i.e. if the zone is shorted out or otherwise incapacitated, the suppression system activation must still report an alarm condition to the monitoring station. There are no written review comments. Associated building permit: BLD10-01904 (BAGUETTE DELI - IDAHO BLDG - 1ST FLR) To remodel a 1,588 sq.ft. existing restaurant created under BLD06-00213 (Cold Stone Creamery) for a new restaurant. Work includes construction of interior non-bearing walls & millwork to create seating, service, work and storage areas as shown on the approved plans to include red-lined notes on plans and all plan review conditions attached to plans by all reviewing agencies. Scope of work includes: installation of new kitchen equipment, installation of a new type I ventless hood, installation of new (Big Dipper) grease trap, and finishes in compliance with chapter 8 of the 2006 IBC. This building is fully sprinklered per 1994 UCBC because it is too tall and has too many stories. **TLW**.
|