Permit Information
Permit NumberFIR10-00569
StatusFinaled
Name CURTIS FIRE SPRINKLER SERVICE INC
Site Address 2900 W MAIN ST
Project NameEBERLESTOCK USA
Customer Number 
ePlanReviewNo
Description
The Fire Sprinkler Scope of work consists of a wet pipe system to protect the storage of backpacks up to 10’ high in cardboard boxes stacked on pallets or the floor (without racks) in a two level building. The design criteria used for the sprinkler system does NOT permit storage >10’. The upper level is only a partial level. The commodity is classified as Class IV miscellaneous storage. The system is supplied by 6” underground through a 4” back flow preventer and a straight gut system in a 1 hour rated enclosure. The piping is side feed with 2½” main and 2” branch lines.

The shell building permit was BLD10-01086
The underground piping was installed under permit FIR10-00497


Building Department Scope:

New office/warehouse tenant in 13,150 sq. ft. cold shell building constructed under BLD10-01086. Work to include... Planning approval done under CUP10-00003 and DRH10-00085. NOTE: This building is fully fire sprinklered.

Contractor’s Note:
The building permit has not been issued at this time. The building department may determine that changes are required to the building plans in order to meet code. These changes may affect the sprinkler system. The sprinkler contractor will be required to make all necessary changes that may be required. Therefore, if the sprinkler contractor chooses to proceed without an issued building permit they will do so on their own cognizance

Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection4/25/20114/25/20114/26/2011PPASS
DetailsForrest France
Fire sprinkler permit work passed final inspection per T. Frost.
INSP-Final Inspection4/22/20114/22/20114/22/2011PPASS
DetailsForrest France
Final passed and forward flow test passed.


don Phone #: ###-####
INSP-Sprinkler Rough-in/Hydro4/22/20114/22/20114/22/2011PPASS
DetailsForrest France
Overhead hydro passed on both floors.

don Phone #: ###-####
INSP-Final Inspection4/19/20114/20/20114/21/2011ANR
DetailsForrest France
Provide sprinkler coverage at the second floor patio room, records indicate an overhead hydrostatic test remains, FDC appears partially obstructed. Outside bell repaired while on site.
INSP-Final Inspection4/19/20114/19/20114/20/2011PNR
DetailsForrest France
Don Phone #: ###-####
INSP-Final Inspection3/25/20113/25/20113/25/2011PNR
DetailsTim Frost
Fire alarm was not ready.

don Phone #: ###-####
INSP-Supply line flush3/25/20113/25/20113/25/2011PPASS
DetailsTim Frost
Flush completed successfully.

don Phone #: ###-####
INSP-Sprinkler Rough-in/Hydro3/8/20113/8/20113/8/2011PDONE
DetailsTim Frost
Hydro passed.
Rough in passed except for adding one brace to the main where a new offset was added. The hydraulics had enough cushion that the offset did not adversely affect the hydraulic calculation. One drop plug in restroom awaiting ceiling.
INSP-Conference3/2/20113/2/20113/3/2011PDONE
DetailsForrest France
Site visit regarding suspended light fixture placement at the east side main level. Upright sprinkler protection does not appear obstructed as currently installed.
INSP-Sprinkler Rough-in/Hydro1/19/20111/20/20111/20/2011APART
DetailsForrest France
Restrooms okayed for ceiling cover. Noted missing hangers one branch piece per line at the deck, inspectors test connections at the riser to be relocated. Full rough-in inspection not complete.