Permit NumberFIR10-00577
StatusFinaled
Name SIMPLEX GRINNELL
Site Address 1150 N CURTIS RD
Project NameUS BUREAU OF REC - CONF RM
Customer Number 
ePlanReviewNo
Description
10/5/11 PLAN MODIFICATION (0 initiating devices affected): This plan modification is to relocate and increase the candela rating of a notification device in a conference room that has been resized since the original review. There are no additional review comments. 11/12/10:This quick permit is to provide door holders, associated smoke detectors for release of the door holders, and a notification device to a conference room close to the main entry area. The new devices are being added to the existing Simplex 4020 panel existing circuits. There are no written review comments. Approval is subject to field measurement of the EOL voltage drop. For appliances with an operating voltage range of 16V – 33V, the minimum acceptable voltage is 19.6V with the AC power off. Any measurement below this voltage will be considered insufficient to run the NACs at the end of useful battery life of 20.4V. UL 864, Standard for Control Units for Fire Signaling Systems. The installing contractor shall have available at final inspection a voltage meter and measure end of line voltages; witnessed by the field inspector. There is no associated building permit.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection5/16/20125/17/20125/17/2012APASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection5/11/20125/16/20125/16/2012AFAIL
DetailsTroy Cobbley
I went ahead and tested the horn/strobe and the smoke detectors for the door release. The devices functioned correctly and the signals received at the central station. The smoke detectors have been centered at the doors. What is not complete are the plans. Per the original correction notice plans needed to be re-submitted or as-builts provided showing the 30cd strobe. The fire alarm vendor chose to re-submit for a plan modification. The problem is the plan modifications show a 110cd strobe where the 30cd has been installed. Also the room size is incorrect and the actual location of the work is in the south end of the building not as shown in the north end of the building. As discussed an accurate as-built package needs to be provided prior to a final sign off.
FIR-Aging Inspection4/18/20124/18/20124/18/2012 NR
DetailsTroy Cobbley
I spoke to Charlie with Simplex several weeks ago and he stated that they were working on this permit.
FIR-Aging Inspection5/2/20115/2/20115/5/2011 NR
DetailsTroy Cobbley
I spoke to Tammy with SimplexGrinnell about getting work completed and the inspection finaled. She is following up and will contact me with the project status.
INSP-Final Inspection1/28/20112/9/20112/9/2011AFAIL
DetailsTroy Cobbley
The smoke detectors for door release shall be centered on the doorway. Also plans will either need to be resubmitted showing the 30cd strobe or as-builts with verification of EOL voltage drop.