Permit Information
Permit NumberFIR10-00616
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 3491 S TK AVE
Project NameB and D Foods
Customer Number 
ePlanReviewNo
Description
The Fire Sprinkler Scope of work consists of protecting a new addition. The addition has a warehouse and freezer. The existing system consists of several trees link to a center feed main. The new addition is a grid with 4”x2½x2” pipe sizing. The system is supplied by 8” Udg with yard Piv through a 6” backflow preventer. There is also a 2½” hose system. The storage arrangement in the new addition is listed in the review..





Building Department Scope:

B and D Foods - Warehouse and Freezer Addition - To construct a 12,585 square foot, one story, pre-engineered metal building warehouse and freezer addition on the east side of an existing 26,000 square foot, one story office and warehouse building. The addition will have within it a 4,340 square foot freezer warehouse and an 895 square foot, wood framed mezzanine above the breakroom/restroom area. This permit also includes related site improvements. All construction per the approved plans and attached comment list. JCM
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/20/20111/21/20111/21/2011PPASS
DetailsForrest France
Noted correction items field verified for completion. Fire sprinkler permit finaled.
INSP-Final Inspection1/19/20111/20/20111/20/2011APART
DetailsForrest France
Overhead install okayed with the exception of one lateral seismic brace at the north end 2 1/2" main. Final pending PRV at the riser and main tie-ins.
INSP-Sprinkler Rough-in/Hydro1/19/20111/20/20111/20/2011APART
DetailsForrest France
Overhead hydrostatic testing at the new addition passed.
INSP-Final Inspection1/18/20111/19/20111/19/2011ANR
DetailsForrest France
justin Phone #: ###-####
INSP-Sprinkler Rough-in/Hydro1/18/20111/19/20111/19/2011ANR
DetailsForrest France
Overhead hydrostatic test not ready due to system impairment.
INSP-Sprinkler Rough-in1/10/20111/11/20111/11/2011APART
DetailsForrest France
Okay to cover grid ceiling areas at rooms below the mezzanine including upright protection below the stairs.