INSP-Final Inspection | 4/11/2011 | 4/12/2011 | 4/12/2011 | A | PASS |
Forrest France
|
|
|
Corrections verified for completion. Acceptance testing passed, fire alarm permit finaled.
|
INSP-Final Inspection | 4/5/2011 | 4/6/2011 | 4/8/2011 | A | PART |
Forrest France
|
|
|
Final pending program changes for accurate solenoid to detector operations at systems 6 and 8. Tampers, low airs, and flows reported okay. New heat detector locations appear acceptable- need to provide appropriate test equipment at next inspection for verification of HD functionality.
|
FIR-Aging Inspection | 3/23/2011 | 3/23/2011 | 3/23/2011 | | PEND |
Forrest France
|
|
|
No call for inspection- Final pending.
|