INSP-Final Inspection | 6/20/2011 | 6/20/2011 | 6/20/2011 | P | PASS |
Forrest France
|
|
|
Verified plan modification and installation of new SW heads and piping at the bonus room above the garage. System charged while on site. Permit finaled.
|
INSP-Final Inspection | 6/1/2011 | 6/2/2011 | 6/2/2011 | A | PART |
Forrest France
|
|
|
Final pending coverage at the finished room above the heated garage due to modified 13D requirements and sec. 8.6.5 NFPA13D. Remainder of installation completed satisfactory including flow switch test.
|
INSP-Sprinkler Rough-in/Hydro | 5/10/2011 | 5/11/2011 | 5/11/2011 | A | CANC |
Forrest France
|
|
|
inspection for UG. please call Trent at ###-#### one hr before inspection. Phone #: ###-#### >> Inspection requested via web by Trent Bice Inspection cancelled from web by: Trent Bice
|
INSP-Sprinkler Rough-in | 5/10/2011 | 5/11/2011 | 5/11/2011 | A | CANC |
Forrest France
|
|
|
request inspection for domestic water line @ same time of UG inspection. Please call Trent @ ###-#### one hr before inspection time. Phone #: ###-#### >> Inspection requested via web by Trent Bice Inspection cancelled from web by: Trent Bice
|
INSP-Supply line flush | 5/6/2011 | 5/6/2011 | 5/6/2011 | P | DONE |
Forrest France
|
|
|
UG supply line flush completed satisfactory.
|
INSP-Sprinkler Rough-in | 3/7/2011 | 3/7/2011 | 3/8/2011 | P | PART |
Forrest France
|
|
|
Overhead install approved for cover.
|
INSP-Sprinkler Rough-in | 3/3/2011 | 3/4/2011 | 3/4/2011 | A | PART |
Forrest France
|
|
|
Overhead install okayed for cover after discussion with contractor on site regarding batt insulation adjustments for cold cavity protection at four locations including the NW bedroom, front hall, kitchen and great room areas.
|
INSP-Sprinkler Rough-in | 2/9/2011 | 2/10/2011 | 2/10/2011 | A | PART |
Forrest France
|
|
|
Overhead rough-in passed inspection, noted sw heads at the garages are not yet installed, riser or supply manifolds are not ready at this time. Contractor to call for inspection of batt insulation at the first floor piping prior to cover- (tented areas okayed).
|