Permit Information
Permit NumberFIR11-00026
StatusFinaled
Name DOHERTY ELECTRIC
Site Address 501 W FRONT ST
Project NameConcordia University Law Schoo
Customer Number 
ePlanReviewNo
Description
This fire alarm permit is to extend an existing manual fire alarm system into the addition. The system is to include new remote power supplies (NAC panels), a remote annunciator, a relocated pull station, full notification, HVAC shutdown/monitoring, In-duct detectors for f/s damper shutdown, relocated modules for existing sprinkler system monitoring; alarm, trouble, and supervisory connections to a preaction system panel in the server room (the actuating smoke detectors are connected to the releasing system panel and are not part of the fire alarm system), heat detectors located at Library Office 133 and the double door entry for actuation of a deluge system water curtain, a relay for server room f/s damper shut down upon activation of the preaction system, and relays and detection devices for elevator recall functions.

Associated building permit: BLD10-01853 Concordia University - To construct a 32,565 square foot, three story addition on the west side of an existing 17,565 square foot, two story building. The interior of first floor of the existing building will be entirely demolished, with the exception of the existing accessible restrooms, shower room, mechanical, electrical and copy/fax rooms. The remaining portion of the existing first floor will be remodeled for 6 foot library book stacks, reading areas, small offices, study rooms and library circulation desk and work areas. The existing mezzanine will be expanded to create a 5,310 square foot second floor that will be used primarily for 6 foot book stacks. This second floor area will also contain a small reading area, small conference room, IT Tech area and three small shared study rooms. The first floor of the new addition will contain two large classrooms, a large waiting area, accessible restrooms, two small study rooms, and four storage areas for various types of storage. The second floor of the new addition will contain four classrooms of varying sizes, a student lounge, a faculty lounge, two accessible restrooms, a chapel, four small conference rooms, a mechanical room and four storage rooms. The third floor of the new addition contains primarily administrative and faculty offices, with one classroom, two large accessible restrooms and unisex accessible restroom. This floor also contains a mechanical room and janitor closet. The foundation was constructed under building permit BLD10-01393. All construction per the approved plans and attached comment list. JCM
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/3/201110/4/201110/4/2011PPASS
DetailsForrest France
Noted corrections verified for completion. Fire alarm permit finaled.
INSP-Final Inspection9/29/20119/30/20119/30/2011AFAIL
DetailsForrest France
The auxiliary power supply arrangement for the IPDACT does not meet product installation guidelines. Wiring must be in accordance with NFPA 70 and 72. Address correction for account monitoring completed while on site.
INSP-Final Inspection8/18/20118/19/20118/19/2011APART
DetailsForrest France
Completed remainder of acceptance testing for the new system. Final pending installation and testing of the new IP-DACT per approved plan.
INSP-Final Inspection8/17/20118/18/20118/18/2011APART
DetailsForrest France
Completed testing for ID and DD at the 1st, 2nd, 3rd floor and roof. Noted address changes at two ID on the first floor and the two RTU's AC1 and AC2. IP-DACT per plan has not been installed- phone lines have been provided interm.
INSP-Final Inspection8/16/20118/17/20118/17/2011PNR
DetailsForrest France
Signals not recieved at central station monitoring. Walkthrough notification testing for the 1st, 2nd and 3rd floors completed acceptable.
INSP-Final Inspection8/8/20118/9/20118/9/2011AFAIL
DetailsForrest France
Noted items during initial walkthrough include 1st floor- provide WP notification devices at shower 140 and unisex 117, notification at study rooms 119A and 119B are overspaced, noted two added ID at store room 115 not shown on plans. 2nd floor- provide signage at the FACP room, install a SD at the panel room, TS, PS and FS at the preaction riser are not shown on plans, hall 212A and 212B notification devices are overspaced/obstructed, IT tech room A/V is overspaced. 3rd floor- casual seating area lacks visual coverage, hall 345 is overspaced. Provide record of inspection and testing including a list of signals per fire code review notes. See also items # 2,3, 7, and 33 on review comments. Post accurate map at the panel. Field modifications including two additional ID, 14 relay modules for AHU shutdown, 4 fire sprinkler monitor modules, and 3 DH to be shown on resubmital plans and matrix as discussed.
INSP-Conference7/13/20117/13/20117/14/2011PDONE
DetailsForrest France
Regarding requirements per IMC 2009 section 606 smoke detection systems control.