Permit Information
Permit NumberFIR11-00038
StatusFinaled
Name AUDIO ELECTRONICS INC
Site Address 908 E JEFFERSON ST
Project NameRoosevelt Elementary
Customer Number 
ePlanReviewNo
Description
This fire alarm permit is to provide a sprinkler monitoring system, smoke detection, pull stations, HVAC monitoring/shutdown, heat detectors and full notification throughout the main building.

Associated building permit: BLD10-01036 Roosevelt Elementary School - (Addition and Remodel) - To insulate the crawl space and basement walls with 6" batt insulation and new 6 mil. vapor retarder at the crawl space floors. To construct a new elevator equipment room in the basement boiler room and a new tele/com room within the maintenance room, as well as, relocate the existing kiln to the east side of the boiler room. To demo and remodel the first floor to redo the accessible restrooms, eliminate the existing kitchen area, relocate the faculty lounge, offices and nurse area to the north side of the corridor and to remove and replace all interior and exterior stairways and ramps, including all railings. To demo and remove the stage area from the south side of the gymnasium. To demo and remodel the second floor to redo the accessible restrooms, add two resource rooms, replace interior stairs with new accessible ramp along corridor #222. To remove and replace existing exterior egress stairway from the library. This permit is also to install new roofing and all new exterior windows and doors, as well as, all new interior finishes throughout. To construct a new 2,140 square foot, two story, wood framed addition, with a 285 square foot elevated loading dock on the northeast corner of the existing building. The addition will have 1,095 square foot warming and serving kitchen on the first floor and a new 1,045 square foot classroom #207 on the second floor. The addition will also include a new elevator in a masonry shaft. This permit also includes related electrical, plumbing and mechanical work, as well as, related site improvements. All construction per the approved plans and attached comment list. JCM
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/8/20118/9/20118/9/2011APASS
DetailsForrest France
Reinspection for noted correction items passed. Fire alarm permit finaled.
INSP-Final Inspection8/5/20118/8/20118/8/2011APART
DetailsForrest France
Correction items include; provide accurate descriptors for initiating devices at the north portable, two H/S at the first floor are not functional, missing FS cover at the sprinkler riser, add PIV descriptor. Remainder of previous c/n items verified for completion.
INSP-Final Inspection8/4/20118/5/20118/5/2011AFAIL
DetailsTroy Cobbley
No inspection was performed due to signal reports not being provided as required per the fire alarm plan review general comments. A correction notice was left with Jerry, the job site superintendant.
INSP-Final Inspection8/3/20118/4/20118/4/2011PFAIL
DetailsTroy Cobbley
Started the fire alarm testing by verifying the fire sprinkler interconnections. When we called the monitoring company I found that no supervisory signals had been received. It appears that account is not set up for these. No further testing was done. Separate phone lines have been verified. Forrest's redline comments have not been verified.
INSP-Final Inspection7/28/20118/1/20118/1/2011AFAIL
DetailsForrest France
See stamped plans for red-lined annotations at the basement, first and second floors regarding noted corrections and adjustments to be made prior to final.
INSP-Alarm Testing7/28/20118/1/20117/28/2011ACANC
DetailsForrest France
Please call Ken with time of test. ###-#### Phone #: ###-#### >> Inspection requested via web by Jason Minnick Inspection cancelled from web by: Jason Minnick