Permit Number | FIR11-00041 |
Status | Finaled |
Name |
SIMPLEX GRINNELL
|
Site Address |
1055 N CURTIS RD
|
Project Name | St Alphonsus south tower |
Customer Number | |
ePlanReview | No |
Description |
This quick permit is to provide one chime/strobe to an existing system due to a tenant improvement. There are no written review comments. Approval is subject to field measurement of the EOL voltage drop. For appliances with an operating voltage range of 16V – 33V, the minimum acceptable voltage is 19.6V with the AC power off. Any measurement below this voltage will be considered insufficient to run the NACs at the end of useful battery life of 20.4V. UL 864, Standard for Control Units for Fire Signaling Systems. The installing contractor shall have available at final inspection a voltage meter and measure end of line voltages; witnessed by the field inspector. Associated building permit BLD10-01733 (ST ALPHONSUS - SOUTH TOWER - 1st FLR - Hyperbaric Chamber Remodel) Permit is to remodel a 574 square foot office area within an existing hospital for two Hyperbaric Chambers. Approval contingent upon adhering to the approved plans on file. Work to include: installation of hyperbaric chambers, installation of new oxygen piping, installation of new accessible counter, installation of new electrical, and finishes in compliance with chapter 8 of the 2006 IBC. This building is fully fire sprinklered any alterations or modifications to the sprinkler system WILL REQUIRE A SEPARATE PERMIT and shall be installed per NFPA #13 as regulated by the fire department. Racking that exceeds 8 ft. in height requires a separate Building Permit be submitted and approved before installation. **TLW**
|