Permit Information
Permit NumberFIR11-00064
StatusFinaled
Name ALLIED GENERAL FIRE & SECURITY
Site Address 5100 W OVERLAND RD
Project NameHillcrest NAC Center
Customer Number 
ePlanReviewNo
Description
3/22/11: PLAN MODIFICATION (20 initiating devices affected): This plan modification is to replace an issued quick permit with full submittals due to the permit scope of work changing, thereby exceeding the allowances for a quick permit. The permit scope of work is to remove two existing NAC panels, re-land the circuits on the existing 5895, add and/or relocate notification devices, and provide new duct detectors due to a tenant improvement. 2/14/11: This quick permit is to temporarily relocate the existing fire alarm panel due to demolition work being done. Under this permit, there is to be no re-circuiting or addition of devices. There are no written review comments. Associated building permit: BLD10-00641 To demolish (Commercial) building at above location in accordance with owner's agreement and $200,000.00 Bond waived per Bob Archibald.
This permit is issued subject to inspector's approval of the sewer cap and site preparation prior to any grading or filling. Note: The Environmental Protection Agency must be notified 10 working days in advance for all renovations that disturb 260 lineal feet/160 square feet/35 cubic feet of asbestos containing materials. Contact the EPA office at 208-378-5746 ref ESC10-00040 & BLD10-00109
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection6/1/20116/1/20116/1/2011PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection5/31/20115/31/20115/31/2011PFAIL
DetailsForrest France
Zones, points and descriptors at offsite monitoring do not accurately correlate with signals transmitted- example; zone 36 point 11 duct detector supervisory reported as zone 11 manual pull station trouble.
INSP-Final Inspection5/27/20115/27/20115/27/2011PFAIL
DetailsTroy Cobbley
Need updated map at the facp showing the correct duct smoke detector addresses and the new pull station at the west exit door. Also the duct detector addresses tested do not correspond with the addresses received at central. To final a map and reverification of duct detector addresses will be required.
INSP-Final Inspection5/26/20115/27/20115/27/2011APART
DetailsTroy Cobbley
Four strobes are over spaced. One strobe needs to be lowered since it is obstructed by duct work. The central station did not receive all of the alarm signals. The inspection had to be stopped due to time constraints. The remaining inspection is scheduled for later today.
INSP-Final Inspection5/25/20115/26/20115/26/2011ACANC
DetailsTroy Cobbley
Cancelled per Tom due to a ground fault on one of the existing circuits. To be rescheduled.