INSP-Final Inspection | 6/1/2011 | 6/1/2011 | 6/1/2011 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Final Inspection | 5/31/2011 | 5/31/2011 | 5/31/2011 | P | FAIL |
Forrest France
|
|
|
Zones, points and descriptors at offsite monitoring do not accurately correlate with signals transmitted- example; zone 36 point 11 duct detector supervisory reported as zone 11 manual pull station trouble.
|
INSP-Final Inspection | 5/27/2011 | 5/27/2011 | 5/27/2011 | P | FAIL |
Troy Cobbley
|
|
|
Need updated map at the facp showing the correct duct smoke detector addresses and the new pull station at the west exit door. Also the duct detector addresses tested do not correspond with the addresses received at central. To final a map and reverification of duct detector addresses will be required.
|
INSP-Final Inspection | 5/26/2011 | 5/27/2011 | 5/27/2011 | A | PART |
Troy Cobbley
|
|
|
Four strobes are over spaced. One strobe needs to be lowered since it is obstructed by duct work. The central station did not receive all of the alarm signals. The inspection had to be stopped due to time constraints. The remaining inspection is scheduled for later today.
|
INSP-Final Inspection | 5/25/2011 | 5/26/2011 | 5/26/2011 | A | CANC |
Troy Cobbley
|
|
|
Cancelled per Tom due to a ground fault on one of the existing circuits. To be rescheduled.
|