Permit Information
Permit NumberFIR11-00072
StatusFinaled
Name SIMPLEX GRINNELL
Site Address 250 E PARKCENTER BLVD
Project NameALBERTSON'S HEADQUARTERS
Customer Number 
ePlanReviewNo
Description
upgrade hood fire system to UL300 standards
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/25/201110/26/201110/26/2011PPASS
DetailsForrest France
Hood suppression system operated correctly under test conditions.
INSP-Final Inspection10/12/201110/12/201110/12/2011PFAIL
DetailsTroy Cobbley
Per Leo, this is a Gaylord system. Per last correspondence with Ansul, all plenum spaces in Gaylord hoods are required to be protected with nozzels. This supression system has not been installed in accordance with those requirements. Forwarded an email to Leo from Ansul/Tyco corporation. No inspection performed.
INSP-Final Inspection10/7/201110/10/201110/10/2011ACANC
DetailsTroy Cobbley
Rod Phone #: ###-#### Rod is on vacation so I called Grinnells office, spoke to Marlene, and then spoke to Leo. He is going to schedule for later in the week.
INSP-Final Inspection10/6/201110/6/201110/6/2011PCANC
DetailsForrest France
Overbooked
FIR-Aging Inspection5/2/20115/2/20115/2/2011ADONE
DetailsForrest France
INSP-Conference2/23/20112/23/20112/23/2011PDONE
DetailsForrest France
On site conference with contractor regarding pull station locations.