Permit Information
Permit NumberFIR11-00098
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 501 W FRONT ST
Project NameConcordia University Law Schoo
Customer NumberCLEAN AGENT
ePlanReviewNo
Description
The Fire Protection Scope of work consists of a HFC-125 clean agent system to protect a computer server room. One 180º nozzle is being utilized with two smoke detectors.


Building Department Scope:

Concordia University - To construct a 32,565 square foot, three story addition on the west side of an existing 17,565 square foot, two story building. The interior of first floor of the existing building will be entirely demolished, with the exception of the existing accessible restrooms, shower room, mechanical, electrical and copy/fax rooms. The remaining portion of the existing first floor will be remodeled for 6 foot library book stacks, reading areas, small offices, study rooms and library circulation desk and work areas. The existing mezzanine will be expanded to create a 5,310 square foot second floor that will be used primarily for 6 foot book stacks. This second floor area will also contain a small reading area, small conference room, IT Tech area and three small shared study rooms. The first floor of the new addition will contain two large classrooms, a large waiting area, accessible restrooms, two small study rooms, and four storage areas for various types of storage. The second floor of the new addition will contain four classrooms of varing sizes, a student lounge, a faculty lounge, two accessible restrooms, a chapel, four small conference rooms, a mechanical room and four storage rooms. The third floor of the new addition contains primarily administrative and faculty offices, with one classroom, two large accessible restrooms and unisex accessible restroom. This floor also contains a mechanical room and janitor closet. The foundation was constructed under building permit BLD10-01393. All construction per the approved plans and attached comment list. JCM

Fire Sprinkler System Design/Spacing:

The room is designed for a minimum concentration of 8.25% at 70ºF in a room of 2120.88 Ft³ in 9.29 seconds utilizing 56# of agent from a 100# cylinder.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/19/20118/22/20118/22/2011PPASS
DetailsForrest France
Site testing and inspection completed acceptable. Permit finaled.
INSP-Final Inspection8/19/20118/19/20118/19/2011PCANC
DetailsForrest France
Overbooked