Permit Information
Permit NumberFIR11-00131
StatusFinaled
Name LEA ELECTRIC LLC
Site Address 300 S 23RD ST
Project NameTERRY REILLY HEALTH SERVICES
Customer Number 
ePlanReviewNo
Description
This fire alarm permit is to provide a new manual system in an existing remodeled building. This permit scope includes partial area smoke detection for door holder release, pull stations, notification, HVAC monitoring/shutdown, and elevator recall functions.

Associated building permit: BLD11-00037 (TERRY REILLY HEALTH SERVICES) (DRH10-00277) This building is NOT fire sprinklered. To remodel an existing 15,195 square foot building (7,101 square foot basement, 7,613 square foot 1st story, 481 square foot 2nd story) and convert it to a medical outpatient clinic. This facility is NOT classified as an ambulatory health care facility because no one will be rendered incapable of self-preservation. Work is to include 6 toilet rooms accessible to the disabled, 2 toilet/shower rooms accessible to the disabled, exterior concrete ramp accessible to the disabled, exterior concrete stairway, exterior steel canopy over the new ramp and stairway, new concrete lintel and jambs at new exterior wall openings, exterior windows and doors, masonry elevator shaft, elevator, interior nonbearing walls, interior windows and doors, new roof covering with insulation installed on top of the roof deck, new roof top HVAC units, gypsum board ceilings, suspended acoustical ceilings, millwork, 1-hr corridors, and interior finishes. The work is required to comply with the approved drawings, the plan review report, and with all applicable codes and ordinances. The fire alarm system is required to comply with NFPA 72 as regulated by the Fire Department. **CJW**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection6/22/20116/23/20116/23/2011APASS
DetailsForrest France
Fire alarm work passed final inspection and testing. Correction items finished, one FSD repaired while on site. As-built drawings recieved.
INSP-Final Inspection6/21/20116/22/20116/22/2011PPART
DetailsForrest France
See review note items # 5, 29 and 35 including one overspaced strobe, one MP to be relocated, provide map at the panel, need as-built plans reflecting the deletion of duct smoke detectors and removal of one non-required WP strobe, elevator test pending, one notification appliance repaired while on site. Walkthrough completed.