Permit Information
Permit NumberFIR11-00136
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 1555 W SHORELINE DR Unit: 210
Project NameLPL Financial Suite 210
Customer Number 
ePlanReviewNo
Description
Shoreline Building
The Fire Sprinkler Scope of work consists of relocating and adding sprinklers to accommodate new wall and ceiling configuration.


Building Department Scope:

Permit is to remodel an existing 2,061 square foot tenant space (Last permitted under BLD95-02186). This building is fire sprinklered to meet high rise provisions. Approval contingent upon adhering to the approved plans on. Work to include: reconfiguration of non-combustible full height partition walls to create 4 larger offices from 5 smaller offices and to separate off a break room, replace existing ceiling with new suspended grid system, new lighting, new accessible doors / hardware, relocate ducts and diffusers, and finishes in compliance with chapter 8 of the 2006 IBC. This building is fully Fire Sprinklered with an approved Fire Alarm system. Any alterations or modifications to the buildings Fire Sprinkler or Fire Alarm system WILL REQUIRE A SEPARATE PERMIT and shall be installed per NFPA 13 & NFPA 72 as regulated by the Boise Fire Department. **TLW**


Fire Sprinkler System Design/Spacing:

Original system hydraulic calculations was a .10 density over 1638 Sqft. flowing 9 sprinklers @ 182 Sqft. on the third floor. The existing system has telescoping branch line piping and 3”, 2½” main piping.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection4/26/20114/26/20114/26/2011PPASS
DetailsForrest France
Fire sprinkler permit work passed final inspection.
INSP-Sprinkler Rough-in3/30/20113/31/20113/31/2011APART
DetailsForrest France
Overhead fire sprinkler modifications okay for cover at the drop ceilings.