Permit Information
Permit NumberFIR11-00139
StatusFinaled
Name ALLIED GENERAL FIRE & SECURITY
Site Address 400 N MILWAUKEE ST
Project NameKOHL’S - FIRE ALARM
Customer Number 
ePlanReviewNo
Description
6/23/11 PLAN MODIFICATION (49 initiating devices affected): This plan modification is to include the required manual fire alarm system. This new permit scope of work is to provide full notification, manual pull stations, a smoke detector above the FACP, devices and modules for elevator recall/shunt trip functions, duct detectors for HVAC monitoring/shutdown, and sprinkler system monitoring.

4/1/11:This fire alarm permit is to replace the existing non-functioning FACP with new and temporarily monitor the sprinkler system until the rest of the required fire alarm system can be installed (the required system shall be submitted under a separate fire alarm permit). An early start request to provide the new panel and sprinkler monitor modules has been approved to avoid a fire watch requirement. This permit scope of work is for the new fire alarm panel and the sprinkler system monitoring only.
Associated building permit: BLD11-00101 KOHL'S DEPARTMENT STORE T.I.- Remodel of a two level, 83,730 sq. ft. (41,741 sq. ft. 1st level / 41,989 sq. ft. 2nd level) mercantile occupancy building, for continued same occupancy use by Kohl's. Kohl's will be an anchor store and is part of the unlimited area BTS Mall. The building is fully sprinklered. Work includes select interior demolition; modification and rebuild of all entry doors; non-combustible metal walls and drywall to create storage room areas, new His & Hers accessible restrooms, office and support areas, training and conference rooms; interior finishes, SAT, shelving, customer dressing rooms; new lighting fixtures, HVAC and plumbing; structural modifications at floor area at new escalator location and for new RTU’s. NOTE: modification to fire sprinkler and or the alarm system cannot be made until a separate permit is issued by the Fire Dept. drs
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/26/20118/29/20118/29/2011APASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection8/24/20118/24/20118/24/2011PFAIL
DetailsTroy Cobbley
Todays inspection was for the the manual pull stations,elevator recall and retesting the wet sprinkler system tamper switches. A manual pull station is required at the lower level east exit doors. The tamper switches did not report to the monitoring station. The outside alarm bell now functions.
INSP-Final Inspection8/18/20118/22/20118/22/2011AFAIL
DetailsTroy Cobbley
Todays inspection included the fire sprinkler interconnections. The tamper switches on the wet/dry risers and low air on the dry riser passed. The wet system flow switch and the dry system pressure switch did not ring the outside alarm bell. Also a walk through on all of the notification devices was performed. See the city approved plans for items needing corrected including the need for additional strobes.
INSP-Final Inspection8/17/20118/19/20118/19/2011ACANC
DetailsForrest France
Overbooked
INSP-Final Inspection8/17/20118/18/20118/18/2011ACANC
DetailsForrest France
Overbooked
INSP-Final Inspection8/16/20118/17/20118/17/2011PFAIL
DetailsTroy Cobbley
Due to inspection load and time constraints the only items tested today were the facp and the three NAC panels. Interconnetion/supervision of these panels and phone line troubles were verified as well as the account address. Wire guage from the NAC panels was verified as well. I noted the smoke detector in the facp room is located too close to a air register.