INSP-Final Inspection | 5/23/2011 | 5/23/2011 | 5/23/2011 | P | PASS |
Forrest France
|
|
|
Final fire alarm testing passed. Correction items are complete. Note: Station Captain J. Rabbit okayed waiver on knox box requirement per review note.
|
INSP-Final Inspection | 5/13/2011 | 5/16/2011 | 5/19/2011 | P | FAIL |
Forrest France
|
|
|
Noted items include; relocate the SD at the captains room a min.of 3' away from the door to the bathroom, provide a strobe only at the public restroom due to excessive db, repair comm. trouble condition at the panel.
|
INSP-Final Inspection | 5/9/2011 | 5/10/2011 | 5/12/2011 | P | FAIL |
Forrest France
|
|
|
C/N items include; provide a WP appliance at the captains RR per red-line notes, study room 113 HD should be changed to a smoke detector, provide a lock at the breaker to the FACP, post signage at the door to the panel room per review note #37, provide an accurate scanable as-built copy reflecting field modifications, repair comm. fault at the panel, knox box per review note #36 may not be required. HD's tested okay, AES not inspected at this time.
|
INSP-Conference | 4/25/2011 | 4/25/2011 | 4/26/2011 | P | DONE |
Forrest France
|
|
|
Regarding appliance locations at the weight room, plan annotations, SD spacing.
|