Permit Information
Permit NumberFIR11-00168
StatusFinaled
Name ENTERPRISE ELECTRIC
Site Address 358 N BENJAMIN LN
Project NameADA COUNTY PARAMEDICS WAREHOUS
Customer Number 
ePlanReviewNo
Description
This fire alarm permit is to extend the fire alarm system from the main building located at 370 Benjamin (installed under FIR11-00010). Included in this permit scope of work is an annunciator, pull station, sprinkler monitoring modules, HVAC monitoring/shutdown, and transient/lightning protection between the buildings (see comment #1 below). The main building fire alarm panel is utilizing an AES RF radio for transmitting the fire alarm signals (installed under FIR11-00156).

Associated building permit: BLD10-01261 Ada County Paramedics Warehouse Maintenance and Repair Facility - To construct a new 7,410 square foot, one story vehicle maintenance, warehouse and office building. This building is constructed of masonry and wood framed exterior and interior walls and steel joist with metal roof deck. This permit also includes related site improvements. All construction per the approved plans and attached comment list. JCM
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection4/21/20114/22/20114/22/2011APASS
DetailsForrest France
Correction items per last inspection verified for completion. Fire alarm permit finaled.
INSP-Final Inspection4/21/20114/21/20114/21/2011PFAIL
DetailsTroy Cobbley
All items tested ok but the signals sent out report a general fire and supervisory signals for both the 358 and 370 addresses. The signal has to be specific for the address. Signals need to be resent from both buildings to verify corrections. The duct smoke detector was missing the sample tube and was installed while I waited. The tamper switch on the PIV was installed backwards and wired backwards and was also repaired while I waited.
INSP-Final Inspection4/20/20114/21/20114/21/2011AFAIL
DetailsTroy Cobbley
Installation does not match plans. The modules that were to be removed are still installed. Also the the wire between the two buildings is supposed to meet requirements in NEC article 800 and it does not. No testing was performed.