Permit Number | FIR11-00197 |
Status | Finaled |
Name |
SIMPLEX GRINNELL
|
Site Address |
11311 W CHINDEN BLVD
|
Project Name | HP BLDG 7 SERVER ROOM VESDA |
Customer Number | |
ePlanReview | No |
Description |
This fire alarm permit is to provide a VESDA system in the server room for the area above and below the ceiling. An electrical room will be covered by smoke detection. Smoke detectors and the VESDA system will trigger a suppression release panel of the preaction system in the server room. Also part of this permit scope of work are relocated pull stations, new pull stations, and one AIM for the sprinkler system monitoring. Ceiling notification will notify the server room.
Associated building permit: BLD11-00544 (HEWLETT PACKARD BLDG 7 - IPG SERVER ROOM) - To remodel a 5,439 sq. ft. area (3 rooms) within an existing office / storage / shipping building, for current and future I.T. infrastructure growth. Work to include: demolition work per plans; install a new raised access floor system, a new ceiling system with relocated lighting, a new hydraulic lift for equipment and ADA access; construct interior UL listed walls, doors and associated hardware per plans; install a new suspended soffit and acoustical ceiling grid systems; frame new interior walls suspended from roof structure; install new exterior concrete pads w/ mechanical units and exhaust systems that will serve the I.T. room; construct new exterior concrete stairs with metal handrails and guards; provide new exterior fascia and wall panel finishes; interior finishes in compliance with chapter 8 of the 2009 IBC; modify the existing fire alarm/sprinkler system to meet tenants needs and be in compliance with current adopted codes. Work per the approved plans, Engineering, and all other reviewing agencies approvals. NOTE: This building is fully sprinklered with 60 foot yards all around for unlimited area based on current occupancy use. A "Letter of Completion / Compliance" is required as a condition of occupancy for this tenant improvement. DRH10-00308 **SRZ**
|