INSP-Final Inspection | 4/17/2012 | 4/17/2012 | 4/19/2012 | P | PASS |
Forrest France
|
|
|
C/N items verified. Fire alarm permit finaled.
|
INSP-Final Inspection | 4/11/2012 | 4/11/2012 | 4/12/2012 | A | PART |
Forrest France
|
|
|
Revision items include; junction box covers, labels at a/v's, remove sample piping at deleted vesda zone 3, relocate smoke detectors for door release service per NFPA 72 at two locations, fire curtain closure rate to comply with NFPA 80 guidelines.
|
FIR-Aging Inspection | 3/22/2012 | 3/22/2012 | 3/22/2012 | | DONE |
Forrest France
|
|
|
In progress
|