Permit Information
Permit NumberFIR11-00238
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 8049 W FAIRVIEW AVE
Project NameCity Buffet Asian Restaurant
Customer Number 
ePlanReviewNo
Description
The Fire Sprinkler Scope of work consists of adding pendent sprinklers due to new wall and ceiling configuration. The new light hazard area will have quick response sprinklers throughout. The kitchen area has standard response sprinklers. Per the building plan review, this is a change of occupancy therefore the current code(s) shall apply

Building Department Scope:

(CITY BUFFET ASIAN RESTAURANT) Remodel combining two former spaces (approximately 2,700 sq. ft. and 5,400 sq. ft.) changing occupancy into a new 7,924 sq. ft. assembly restaurant space in existing shopping center per approved plans. Work to include select interior demolition of non-structural walls, finishes, electrical, mechanical, & plumbing with modifications to sprinkler and alarm system to be under separate permit as regulated by the fire department. There is an existing 1-hour fire rated wall creating the boundaries between tenants on north and south. Construct new walls to create the entrance / check-in area; kitchen / preparation area; storage, cooler , freezer units; accessible men's & women's restrooms and accessible route; and a private dining area. Interior finishes, electrical, mechanical, plumbing, sprinkler, alarm and Type I grease duct, hood & exhaust system and Type II hood & exhaust system with non-combustible support to structure above. NOTE: This existing building is fully fire sprinklered with 60 feet clearance all around for unlimited area (includes Shopko & strip mall areas). Occupancy use groups other than "B/M/F/S" cannot exceed 10% of existing building area under original UBC codes. The three "A2" occupancy max out the allowed 10% allowed for original building review process. drs

Fire Sprinkler System Design/Spacing:

The existing system is a grid with 2½”x2½”x1½” pipe sizes. The existing system was calculated for Ordinary Hazard II .19/1500. The tenant requires Light Hazard and Ordinary Hazard Group I. Based on a new flow test the existing sprinkler system will no longer achieve the design density.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection9/19/20119/20/20119/19/2011APASS
DetailsTroy Cobbley
permit finaled. owner is removing the palm fronds that are blocking the sidewall protection in the seating area.
INSP-Sprinkler Rough-in7/7/20117/8/20117/8/2011APASS
DetailsTroy Cobbley
The piping in the modified soffit area is ok to cover.
INSP-Sprinkler Rough-in7/5/20117/5/20117/6/2011PPART
DetailsTroy Cobbley
Rough-in passed but piping has been modified in the Buffett area to sidewall coverage that has been installed in a large soffit. Contractor to get with Tim Frost on possible plan modifications due to the changes. Piping is ok to cover except in this area. Additional dry pendants are to be added in the three coolers to provide coverage behind the coil units.