Permit Number | FIR11-00244 |
Status | Finaled |
Name |
SIMPLEX GRINNELL
|
Site Address |
350 N MILWAUKEE ST
|
Project Name | BOISE TOWN SQUARE SERVICE ELEV |
Customer Number | |
ePlanReview | No |
Description |
3/20/12 PLAN MODIFICATION (1 device affected): This quick permit plan modification is to provide additional as-built information - replacing an elevator lobby smoke detector with a heat detector and removing non-required hat-light function modules. Per the contractor, the smoke detector is being replaced with a heat detector because the lobby doors are constantly open to the exterior and are causing false alarms and problems with the smoke detector (see heat detector data sheet in submittal documents). There are no written review comments. Please see redlines on plans. 10/10/11 PLAN MODIFICATION (no devices affected): This plan modification is to provide as-built information (i.e. field changes exceeding field approval) 6/2/11:This quick permit is to provide detection and controls for elevator recall and shunt trip services/functions in the service elevator. There are no written review comments. There is no associated building permit.
|