INSP-Final Inspection | 8/8/2011 | 8/8/2011 | 8/8/2011 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Sprinkler Rough-in | 7/28/2011 | 7/28/2011 | 7/29/2011 | P | PASS |
Troy Cobbley
|
|
|
Protection has been provided under the platform.
|
INSP-Sprinkler Rough-in | 7/25/2011 | 7/26/2011 | 7/26/2011 | A | PASS |
Troy Cobbley
|
|
|
Need to have as-builts and provide coverage beneath the audio/visual booth. All other work is complete.
|
INSP-Sprinkler Rough-in | 7/13/2011 | 7/13/2011 | 7/13/2011 | P | PASS |
Troy Cobbley
|
|
|
See the city approved plans for sprinkler heads marked "ok" where piping can be covered.
|
INSP-Sprinkler Rough-in | 7/5/2011 | 7/6/2011 | 7/6/2011 | A | PASS |
Troy Cobbley
|
|
|
The sprinkler piping on the east side of the fire wall, first floor, is ok to cover.
|
INSP-Sprinkler Rough-in | 6/30/2011 | 7/1/2011 | 7/1/2011 | P | PART |
Troy Cobbley
|
|
|
The first floor piping, east side of wall, piping passed rough-in inspection. Before a cover approval can be given the insulation needs to be repaired. Also three 2" 90's and an elevation change has been installed on this pipe. Provide verification with Boise City plan review to verify that the hydraulic calculations have not been adversly affected. Provide aux drain as discussed.
|
INSP-Sprinkler Rough-in | 6/22/2011 | 6/23/2011 | 6/23/2011 | P | PART |
Forrest France
|
|
|
See plans marked with today's date for areas inspected. Provide seismic clearance at the intersection of the floor and new 2' line.
|