Permit Information
Permit NumberFIR11-00302
StatusFinaled
Name SIMPLEX GRINNELL
Site Address 8775 W USTICK RD
Project NameCOLE VALLEY COMMUNITY SCHOOL/C
Customer Number 
ePlanReviewNo
Description
This fire alarm permit is to extend the existing manual system in to the remodeled area, provide a voice evacuation notification system in the remodeled half of the building, duct detectors for HVAC monitoring/shutdown, smoke detectors above control panels and for door release, door holders, and kitchen hood monitoring.
Associated building permit: BLD11-00279 (COLE COMMUNITY CHURCH & COLE VALLEY CHRISTIAN SCHOOL) Remodel of an existing 34,410 sq. ft. building, constructing a modified 2-hour fire wall per approved alternate to divide into two buildings for allowable area compliance based on Type of Construction, per approved plans. Work to include select interior demolition, upgrading an existing wall to meet an alternate method fire wall, adding a fire alarm/voice evacuation system, new emergency lighting, reconstructing an egress stairway in conjunction with new exterior exit door, constructing an interior vestibule, and modify electrical, sprinkler and alarm systems. NOTE: Alternate approval regarding fire wall attached to this case. NOTE: This building is fully fire sprinklered for allowable area increase with modification on both sides of fire wall for increase of wall integrity per the approved alternate. drs
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/11/20118/12/20118/12/2011APASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection8/9/20118/11/20118/11/2011AFAIL
DetailsTroy Cobbley
HVAC units 213 and 214 did not shut down immediately upon detection of smoke. All other devices tested ok.
INSP-Final Inspection8/8/20118/8/20118/8/2011PFAIL
DetailsTroy Cobbley
See the city approved plans for redline corrections. No devices have been tested except for main level audibility which was ok.
INSP-Final Inspection8/4/20118/5/20118/5/2011PCANC
DetailsTroy Cobbley
To be rescheduled for monday per phone conversation with colton Phone #: ###-####