Permit Number | FIR11-00325 |
Status | Finaled |
Name |
FIRE SENTRY SYSTEMS
|
Site Address |
1301 N ORCHARD ST
|
Project Name | Correctional Industries |
Customer Number | |
ePlanReview | No |
Description |
This quick permit is to provide new modules to monitor a new sprinkler flow switch and two new backflow preventor tamper switches. The addressable devices will be tied in to the existing fire alarm system. There are no written review comments. Associated building permit: BLD11-00832 (CORRECTIONAL INDUSTRIES – CSC Building – entire 1st floor) Permit is to expand an existing 6,627 square foot 1st floor tenant into the entire 1st floor making them 17,910 square feet. This tenant will be vacating the 1,900 square feet they originally occupied on the 2nd floor under BLD07-03252. This building is fully fire sprinklered for area increase. Approval contingent upon adhering to the approved plans on file. Work to include: [installation / demolition of interior partition walls to create additional open office area, six additional offices, and two additional storage rooms], installation of new lighting, installation of new doors / accessible hardware, and finishes in compliance with chapter 8 of the 2009 IBC. This building is fully Fire Sprinklered with an approved Fire Alarm system. Any alterations or modifications to the buildings Fire Sprinkler or Fire Alarm system WILL REQUIRE A SEPARATE PERMIT and shall be installed per NFPA 13 & NFPA 72 as regulated by the Boise Fire Department.**TLW**
|