Permit Information
Permit NumberFIR11-00343
StatusFinaled
Name AUDIO ELECTRONICS INC
Site Address 825 W FORT ST
Project NameST. JOSEPH’S ELEM. REMODEL & E
Customer Number 
ePlanReviewNo
Description
This fire alarm permit is to extend the existing manual fire alarm system in to the remodeled and added areas. The scope includes smoke detectors, notification, pull stations, and duct detectors. A new remote power supply is being provided to accommodate the additional notification. The new initiating devices are to be tied in to the existing fire alarm panel SLC.

Associated building permit: BLD11-00416 (ST. JOSEPH'S ELEMENTARY SCHOOL - EXPANSION) To add a two story, 7,189 sq. ft. addition on the south side of existing gym. Work includes completely demolishing a 2,400 sq. ft. one story structure attached to the south side of gym; and select interior demolition on the 1st & 2nd floor of existing school in area of new addition. Construct footings / foundation for new 2-story addition on south side of gym; exterior & interior walls, floor and roof systems; interior corridor and stairway; finishes, millwork, mechanical, electrical, plumbing, sprinkler and alarm system modifications; accessible interior and exterior route, accessible restrooms and drinking fountains. All per reviewed plans. drs
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection11/4/201111/7/201111/7/2011PPASS
DetailsForrest France
C/N items finished, plan modifications verified. Reinspection passed, fire alarm permit finaled.
INSP-Final Inspection10/12/201110/13/201110/13/2011AFAIL
DetailsTroy Cobbley
When testing the two second floor manual pull stations, as noted on the previous correction entry, I found that they reported to the panel as "zone 15". Per the plans they should be on zone 5. Per the technician all of the smoke detectors and manual pull stations on the second floor are on zone 15. The possible problem is per NFPA and the manufactures listing only a certain amount of powered devices can be placed on each zone. The new device count needs to be verified and if under the limits, as-builts and a new map at the facp is needed. If the count per circuit has been exceeded plan modifications are required. Also there is an issue with water flow alarms being sent from the new water flow switch. See the project related fire alarm permit for specifics.
INSP-Final Inspection10/5/201110/6/201110/6/2011PFAIL
DetailsForrest France
Two non-functional MP stations at the 2nd floor need repaired, flow switch at the main riser is not operable. Notification testing, sprinkler riser supervision, new and relocated SD's tested okay.
INSP-Final Inspection8/23/20118/23/20118/25/2011PNR
DetailsForrest France