Permit Information
Permit NumberFIR11-00355
StatusFinaled
Name ALLIED GENERAL FIRE & SECURITY
Site Address 825 W FORT ST
Project NameSt. Joseph's Elementary School
Customer Number 
ePlanReviewNo
Description
The Fire Sprinkler Scope of work consists of adding fire protection to a new wing of a school. In addition, an area adjoining the new addition is also being remodel. The building and new building extensions have two levels. The area above the lower level has a non-combustible interstitial space. Above this space is a combustible space, partially filled with insulation. A portion of the combustible space will be protected with concealed space sprinklers. There is above and below protection throughout the remodel area. The system has one riser and no floor control valves. Since this is, primarily an existing system the plan reviewer is not requiring floor control valves on the new extension because it is impractical. The system is a mixture of a tree, grid, and loop mains with telescoping branch line piping.


Building Department Scope:

(ST. JOSEPH'S ELEMENTARY SCHOOL - EXPANSION) To add a two story, 7,189 sq. ft. addition on the south side of existing gym. Work includes completely demolishing a 2,400 sq. ft. one-story structure attached to the south side of gym; and select interior demolition on the 1st & 2nd floor of existing school in area of new addition. Construct footings / foundation for new 2-story addition on south side of gym; exterior & interior walls, floor and roof systems; interior corridor and stairway; finishes, millwork, mechanical, electrical, plumbing, sprinkler and alarm system modifications; accessible interior and exterior route, accessible restrooms and drinking fountains. All per reviewed plans. Drs
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection11/7/201111/8/201111/7/2011APASS
DetailsForrest France
Final walkthrough completed. Contractor to provide outside bell signage and repair one DP escutcheon as discussed. Permit finaled. Note: Inspection completed 11/7.
INSP-Final Inspection10/12/201110/13/201110/13/2011AFAIL
DetailsTroy Cobbley
The new flow switch has been installed but when testing it the outside alarm bell would barely ring and then quit. And then 10 to 20 seconds later would ring again and then quit. This was an issue years ago with Ames backflow preventors but this one is a Wilkins. It finally activated the fire alarm panel but this issue needs addressed so that the bell continues to ring when the flow switch is activated.
INSP-Final Inspection10/6/201110/6/201110/6/2011PPART
DetailsForrest France
Final walkthrough completed, minor adjustments done while on site. Verified added head at the dry valve room. Fire alarm interconnections tested. Final pending repair of non-functional waterflow switch at the main riser.
INSP-Sprinkler Rough-in/Hydro10/5/201110/6/201110/6/2011APASS
DetailsForrest France
OH hydrostatic re-test passed.
INSP-Sprinkler Rough-in10/4/201110/5/201110/5/2011AFAIL
DetailsForrest France
Hydrostatic test of the overhead system failed due to a 10 psi. pressure loss at the guage. Relocated heads at the 1st floor corridor and 2nd floor utility rooms okayed.
INSP-Sprinkler Rough-in9/28/20119/30/20119/30/2011AFAIL
DetailsForrest France
Upright heads at the first floor corridor are blocked by adjacent truss webs due to distance of the deflector from the deck, two pendent heads at classroom 201 need to meet fig. 8.6.5.1.2(b) NFPA 13, storage room 204 uprights are obstructed by ductwork. Remainder of drop ceiling areas are okay for cover.
INSP-Sprinkler Rough-in9/23/20119/23/20119/23/2011PPART
DetailsForrest France
See plans for annotations regarding areas inspected to date.
INSP-Sprinkler Rough-in9/20/20119/20/20119/20/2011PPART
DetailsForrest France
Reinspection for the second floor classrooms and 1st floor RR completed. Okay for cover at rooms 203, 205 and 206 new addition- noted one missing seismic brace at room 203. Restrooms 1st floor east side also approved for cover.
INSP-Sprinkler Rough-in9/16/20119/16/20119/16/2011PFAIL
DetailsForrest France
Inspection for cover at the three 2nd floor classrooms and both the 1st floor restrooms failed due to obstructed heads, one missing head, missing seismic bracing, sprig in need of adjustment, access, etc.
INSP-Sprinkler Rough-in/Hydro9/6/20119/6/20119/6/2011APART
DetailsForrest France
See approved plans for marked and dated locations inspected to date.
INSP-Sprinkler Rough-in8/30/20118/30/20118/31/2011APART
DetailsForrest France
Reference stamped plan set for locations inspected today including the 1st floor restrooms east side, under stairway heads, and the 2nd floor classroom remodel.
INSP-Sprinkler Rough-in8/25/20118/25/20118/25/2011PPART
DetailsForrest France
Verified corrections at the administration area and kindergarden classroom, okay to sheetrock the deck only at classrooms 113 and 115. Discussed possible obstruction issues at the soffit in rooms 113 and 115.
INSP-Sprinkler Rough-in/Hydro8/10/20118/12/20118/12/2011APART
DetailsForrest France
Inspection completed for portions of the 1st and 2nd floors remodeled and new additions as marked on stamped plan set. Noted items include; 1st floor- missing 4 seismic braces, overspaced uprights at room 101 and 109, 2nd floor- pipe sizing at room 200 does not match plan, need to sheetrock concealed space or provide sprinkler protection, provide clearance at the floor for the 2" dry feed to the wheelchair ramp. Okay to cover new exterior canopy and ceiling above the ramp.