Permit Information
Permit NumberFIR11-00366
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 650 N ARMSTRONG PL
Project NameWinco Foods Records Retention
Customer Number 
ePlanReviewNo
Description
The Fire Sprinkler Scope of work consists of cardboard carton record storage. There will be approximately 335’ of C-900 6” underground with necessary thrust blocks to a previously installed IBR, a new riser with backflow preventer, a wall piv and remote FDC. The system is a 4”x3”x1½” grid. There is an outlet left for a future second floor.

The IBR was installed under permit FIR11-00285
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection9/19/20119/19/20119/19/2011PPASS
DetailsTroy Cobbley
Permit finaled.
INSP-Final Inspection9/19/20119/19/20119/19/2011PPASS
DetailsTroy Cobbley
Permit finaled. Forward flush passed
INSP-Final Inspection9/16/20119/16/20119/16/2011PCANC
DetailsTroy Cobbley
over booked
INSP-Final Inspection9/15/20119/15/20119/15/2011PCANC
DetailsTroy Cobbley
To be canceled per lonnie
INSP-Final Inspection9/6/20119/6/20119/6/2011PFAIL
DetailsTroy Cobbley
Need the forward flush passed and the fire alarm interconnections tested.