Permit Information
Permit NumberFIR11-00378
StatusFinaled
Name AUDIO ELECTRONICS INC
Site Address 440 N CLOVERDALE RD
Project NameACHD TIRE SHOP EXPANSION
Customer Number 
ePlanReviewNo
Description
10-10-11 PLAN MODIFICATION (no additional initiating devices affected): This plan modification is to change the fire alarm pane from a Silent Knight 5104B to a Silent Knight 5208. In addition, the previous submittal indicated monitoring for a wet sprinkler system, however it is actually a dry system, therefore the quantity and type of devices being monitored has been revised.

8-4-11:This fire alarm permit is to provide a new fire alarm panel for sprinkler system monitoring. Included in this permit scope of work is a pull station, a voluntary smoke detector above the FACP, monitoring the sprinkler system valves, and voluntarily monitoring the Knox box.

Associated building permit: BLD10-02865 Ada County Highway District Tire Shop Expansion - To demolish and remove two small sheds and construct a 1,545 square foot, one story, masonry wall and wood framed tire shop expansion and related site improvements. The expansion will be located on the west side of an existing 1,535 sq. ft., one story shop building. The expansion will include a 1,030 square foot, tire storage area, a 185 square foot break room with an attic access floor above and a 330 square foot, tank storage room. This permit also includes updating the lighting at the existing shop building. All construction per the approved plans and attached comment list. JCM
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/19/201110/20/201110/20/2011APASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection10/18/201110/19/201110/19/2011PFAIL
DetailsTroy Cobbley
The technician did not have a "butset" to verify the phone numbers that have been set up for the new facp. No inspection was performed.
INSP-Final Inspection10/17/201110/18/201110/18/2011PCANC
DetailsTroy Cobbley
Troy, Please let me know an approximate time, so I can let everyone know. Jason ###-#### Phone #: ###-#### >> Inspection requested via web by Jason Minnick Inspection cancelled from web by: Jason Minnick
INSP-Final Inspection9/22/20119/23/20119/23/2011AFAIL
DetailsTroy Cobbley
A model 5230 remote annunciator has been installed on the face of the panel so that alarm functions are provided per IFC 906. After starting the testing it was found that the manual pull station when put in the normal "off alarm" condition the panel would self restore which is not allowed. Per NFPA 72 - 23.8.2.9 the panel can only be reset at the panel itself, not at this initiating device. Also in the course of researching this I was notified by the fire alarm panel manufacture that this panel is not listed for stand alone applications but is listed as a dialer. A panel needs to be installed that meets the intended application and this shall be submitted to the city for review as a plan modification.
INSP-Final Inspection9/22/20119/22/20119/22/2011PCANC
DetailsTroy Cobbley
Was not able to test the fire alarm since the fire sprinkler contractor had not been scheduled to test the dry system
INSP-Final Inspection9/20/20119/20/20119/20/2011PCANC
DetailsTroy Cobbley
Jason Phone #: ###-####
INSP-Final Inspection9/19/20119/20/20119/20/2011AFAIL
DetailsTroy Cobbley
There is no audible or visual annunciation of an alarm condition at the fire alarm panel as required by IFC 906. Burl is going to install a remote annunciator at the panel and re-inspect for this afternoon.