Permit Information
Permit NumberFIR11-00380
StatusFinaled
Name SIMPLEX GRINNELL
Site Address 6140 W CURTISIAN AVE
Project NameSARMC MOB6 STERIOTAXIS LAB
Customer Number 
ePlanReviewNo
Description
11/7/11 PLAN MODIFICATION (19 initiating devices affected): This plan modification is to add 7 new in-duct detectors, relocate 10 existing in-duct detectors, and relocate 7 notification devices due to building plan changes.

8/12/11:This fire alarm permit is to provide a NAC panel to accommodate new notification devices and tie in new initiating devices to the existing signal line circuit due to a tenant improvement. Included in this permit scope are notification devices, an annunciator at Nurse’s Station 301, a pull station, an in-duct detector for f/s damper shutdown, and nine new smoke detectors.

Associated building permit: BLD11-00923 (ST. ALS - MOB #6) (STEREOTAXIS LAB - THIRD FLOOR) Remodel of an existing 3,100 sq. ft. portion of the third floor of an existing medical office building. Work to include select interior demolition of non-structural partitions, finishes, millwork, etc. New work includes construction of new interior non-bearing walls to include the previous CT Scan Waiting & Reception area to become part of the relocated Control, Changing and access / egress path; interior walls to modify or create Lab, Work Area and Equipment rooms; new framed walls, fire-retardant treated wood or metal, around the Lab in accordance with requirements for adding additional RF lead shield for walls, glass, frames and doors as indicated on plans; structural modifications for installation of new medical equipment; protection and repair of existing fire-resistive assemblies; work on electrical, plumbing, mechanical, medical gas, fire suppression and alarm systems. All per approved plans, notes and all attached plan review comments / conditions. NOTE: This building is fully fire sprinklered. drs
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection12/20/201112/21/201112/21/2011APASS
DetailsTroy Cobbley
permit finaled
INSP-Alarm Testing11/29/201112/1/201112/1/2011AFAIL
DetailsTroy Cobbley
The strobes in the four patient rooms are overspaced. The two smoke detectors in the restrooms between the patient rooms are missing and will need to be installed or ok'd by plan review to remain deleted. The smoke detector at the double doors to the pedestrian walkway was left above the ceiling. The lone smoke detector that was left in the main corridor after the double doors were demo'd needs to be removed.