Permit Information
Permit NumberFIR11-00395
StatusFinaled
Name ALLIED GENERAL FIRE & SECURITY
Site Address 8501 W FRANKLIN RD
Project NameDESIGNER SHOE WAREHOUSE
Customer Number 
ePlanReviewNo
Description
The Fire Sprinkler Scope of work consists of converting an existing high pile rack sprinkler system into an ordinary hazard group II mercantile sprinklers system. A new demising wall is being added to separate receiving area from the sales area. Sprinklers are being added to correct spacing issues created by the new wall. The owner’s certificate and an email from the designer indicates “There will be no storage of synthetic rubber or plastics over 5’-0”. There are no racks anywhere in the building, in the receiving the shoes are taking directly to the sales floor and placed onto the display shelves which are 4’-0” in height.” Sprinklers are also being added to a new office area. A new storage area is being added. The new wall locations cause sprinkler spacing issues. Therefore, sprinklers are being added around the new storage area walls. A new vestibule with a suspended ceiling is being added. A new pendent sprinkler will be dropped into the vestibule. There are several locations where sprinklers are being added or moved due to obstructions. The system is approved for a maximum of 109 Sqft spacing.

The demolition work was performed under permit FIR11-00363

Building Department Scope:

(DESIGNER SHOE WAREHOUSE) Remodel of an existing 25,015 sq. ft. space for a new retail shoe store tenant in existing building per approved plans. Work to include select interior demolition of walls, ceiling grid, fixtures and finishes as indicated in plans. New work includes new interior partitions to create storage areas, office, lounge and accessible restrooms, sales / display areas, areas of perimeter walls furred-out; hard lid and suspended ceiling grid systems in specific minor locations; new fixtures; new vestibule; electrical, mechanical, plumbing, fire suppression and alarm system modifications and interior finishes. NOTE: This building is fire sprinklered for increased building area and for fire area. drs
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Sprinkler Rough-in/Hydro9/21/20119/22/20119/21/2011APASS
DetailsTroy Cobbley
Permit finaled. The storage racking has been modified to be 4'-0" in height. Brice, the general contractor, has been notified that the storage on these shelves can not exceed 5'-0" in height.
INSP-Sprinkler Rough-in9/16/20119/16/20119/16/2011PFAIL
DetailsTroy Cobbley
Remove the masking tape from the upright heads in the riser room. Replace the painted head over the facp. Resubmit plans addressing the rack storage which is not allowed per the existing scope of work.