Permit Information
Permit NumberFIR11-00397
StatusFinaled
Name CURTIS FIRE SPRINKLER SERVICE INC
Site Address 1778 S TOLUKA WAY
Project NameLasher Residence
Customer Number 
ePlanReviewNo
Description
Permit for the construction of a 3,923 sq. ft., three story (basement 771 sq. ft., second story 511 sq. ft., third story 2,641 sq. ft.) single family dwelling with 4 bedrooms, 3 1/2 bathrooms, approximately 207 sq. ft. of covered patio and a 1,057 sq. ft. attached garage per the approved plans, plan review report and any notations.This project is located in the WUI zone A. Construction must comply with these standards, including the requirement for 30' of defensible space. A letter from the applicant’s geotechnical engineer indicating that the footing sub-grade is acceptable must be approved by Public Works prior to scheduling a footing inspection. Call Terry Records at 384-3946. R-1A zoning and setbacks per planning. Fire sprinklers are required. CDM

Fire Protection Requirements;
This home must be equipped with a modified 13 D sprinkler system. The sprinklers protection is to include ALL closets, baths and garages. -TRF-
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection11/17/201111/18/201111/18/2011APASS
DetailsForrest France
Correction items field verified, outside bell tested okay. Note: light fixtures at some locations are not installed- be aware of possible obstruction issues that may develop due to fixture type and size.
INSP-Final Inspection11/15/201111/16/201111/16/2011AFAIL
DetailsForrest France
Missing backflow certification, control valves need locked or sealed in the open position, riser is not secured to the structure, inspectors test and drain does not terminate outside, noted leaking feed main in the crawlspace.
INSP-Final Inspection11/14/201111/15/201111/15/2011ADEFR
DetailsForrest France
Don Phone #: ###-####
INSP-Sprinkler Rough-in9/8/20119/8/20119/8/2011PPART
DetailsForrest France
Inspection for cold cavity protection completed acceptable. Overhead install approved for cover.
INSP-Sprinkler Rough-in9/7/20119/7/20119/7/2011PNR
DetailsForrest France
Don Phone #: ###-####
INSP-Sprinkler Rough-in8/31/20119/1/20119/1/2011APART
DetailsForrest France
Overhead rough-in okayed. Approval for cover pending cold cavity protection verification.