Permit Number | FIR11-00398 |
Status | Finaled |
Name |
CRANE ALARM COMPANY
|
Site Address |
8645 W FRANKLIN RD
|
Project Name | A.T. SOLUTIONS BATHROOM |
Customer Number | |
ePlanReview | No |
Description |
This quick permit is to provide notification in the new restroom and notification in the corridor/hallway created by the new restroom walls. See redlines on the drawings. There are no written review comments. Approval is subject to field measurement of the EOL voltage drop. The voltage drop calculations are based on a 10% drop, therefore the minimum acceptable voltage is 21.6V with the AC power off. Any measurement below this voltage will be considered insufficient to run the NACs at the end of useful battery life of 20.4V. UL 864, Standard for Control Units for Fire Signaling Systems. The installing contractor shall have available at final inspection a voltage meter and measure end of line voltages; witnessed by the field inspector. Associated building permit: BLD11-01132 A.T. SOLUTIONS BATHROOM- Permit for minor tenant improvements to an existing 13,550 sq. ft tenant space with work to include the construction of a new ADA compliant restroom. The existing light fixtures will be repositioned and no additional fixtures will be installed. This space does not require additional restroom fixtures per the occupant load but are being added for the convenience of the occupants. CDM
|