Permit Information
Permit NumberFIR11-00399
StatusFinaled
Name ALARMCO
Site Address 12065 W MCMILLAN RD
Project NameFIRE STATION #10
Customer Number 
ePlanReviewNo
Description
This fire alarm permit is to provide a non-required manual system with performance-based automatic smoke detection. The system includes full notification, partial smoke detection, pull stations, and heat detectors. An AES RF Radio is being provided instead of the DACT with an IntelliTap. No HVAC has been shown on the plans. There is no associated building permit.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/17/201110/17/201110/17/2011PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection10/11/201110/12/201110/12/2011AFAIL
DetailsTroy Cobbley
Signals are now being reported correctly. As-builts/Intelipro information was not provided as requested by plan review.
INSP-Final Inspection9/30/20119/30/20119/30/2011PFAIL
DetailsTroy Cobbley
Tested the flow switch, tamper #1 and main lobby pull station. Paul received the signals from the relays but no informaton from the intela tap came in.
INSP-Final Inspection9/28/20119/28/20119/28/2011PFAIL
DetailsTroy Cobbley
Tamper #1 needs adjusted, could not find the inspectors test valve so the flow switch was not tested. Also need the tamper switch and manual pull stations addresses on the panel to match the map and what is reported to central station. All other items were tested. Horns did not sync but Gary fixed this while I waited.
INSP-Final Inspection9/26/20119/26/20119/26/2011PFAIL
DetailsTroy Cobbley
Did not perform the testing due to the intella tap not being installed on the AES dialer.
INSP-Final Inspection9/21/20119/22/20119/22/2011AFAIL
DetailsTroy Cobbley
See the city approved plans for locations of corrections needed. No actual testing was performed
INSP-Conference8/31/20118/31/20118/31/2011PDONE
DetailsTroy Cobbley
Performed site visit to determine placement of heat detectors and found that the city approved plans do not show the heat detectors spaced for "sloped" ceilings, "High" ceilings or spacing taking "beam construction" into account. The plans also do not reflect the existing fire sprinkler riser which includes two interior tamper switches, an exterior wall PIV and a flow switch. After a discussion with plan review it was determined that a plan modification/resubmittal is needed to show this information. This was relayed to the fire alarm tech.