Permit Number | FIR11-00440 |
Status | Finaled |
Name |
SIMPLEX GRINNELL
|
Site Address |
11311 W CHINDEN BLVD
|
Project Name | HP BLDG 5-LEGAL FOCUS ROOMS |
Customer Number | |
ePlanReview | No |
Description |
This quick permit is to provide two strobe only notification devices and tie them in to an existing circuit to accomodate a tenant remodel. Approval is subject to field measurement of the EOL voltage drop. For appliances with an operating voltage range of 16V – 33V, the minimum acceptable voltage is 19.6V with the AC power off. Any measurement below this voltage will be considered insufficient to run the NACs at the end of useful battery life of 20.4V. UL 864, Standard for Control Units for Fire Signaling Systems. The installing contractor shall have available at final inspection a voltage meter and measure end of line voltages; witnessed by the field inspector. There are no written review comments. Associated building permit: BLD11-01319 (HP BLDG 5 - LEGAL FOCUS ROOMS) Construct two offices about 100 sq/ft each using two existing walls adding two doors and about 40 ft of new wall,
|