Permit NumberFIR11-00442
StatusFinaled
Name AUDIO ELECTRONICS INC
Site Address 514 S 12TH ST
Project Name12th & River Senior Apartments
Customer Number 
ePlanReviewNo
Description
This fire alarm permit is to provide a manual fire alarm system in a new building. This permit scope shall include a remote annunciator panel, a pull station, smoke detection above the panels, full notification, devices for elevator recall and shunt trip functions, sprinkler system monitoring, smoke detectors for magnetic door holder release, and in-duct detectors for damper shutdown. Per the contractor, the single- and multiple-station smoke alarms are by others.

Associated building permit: BLD11-00179 (12th & River Senior Apartments) To construct a three story, 53 unit, senior apartment housing with enclosed parking and associated amenities, a total area of 60,279 sq. ft. (1st - 22,940 sf / 2nd - 18,737 sf / 3rd - 18,602 sf). There are 52 units of 614 sf and one unit of 772 sf. There are three Type 'A' Accessible units and 50 Type 'B' Accessible units. Building is wood frame non-rated construction, fully sprinklered with NFPA 13 system; 1/2 hour fire-resistive fire partitions for corridor wall & corridor lid construction; walls between sleeping units / dwelling units shall be 1/2 hour fire-resistive fire partitions; 1/2 hour horizontal fire-resistive assembly between units and between other occupancies unless a full 1-hour assembly is required to separate mixed use occupancies; 1-hour fire-resistive fire barrier walls and 1-hour fire-resistive horizontal assemblies between mixed use occupancies of "A" & "R" and "R" & "S2" (sheet A0.1) and at stair enclosure separation. Electrical, mechanical, plumbing, fire sprinkler and alarm systems; interior finishes and millwork in accordance with reviewed plans and all attached plan reviews and red-lined comments of all reviewing agencies. drs
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection7/16/20127/16/20127/16/2012PPASS
DetailsForrest France
Corrections and remainder of acceptance testing completed satisfactory. Fire alarm permit finaled.
INSP-Final Inspection7/13/20127/16/20127/16/2012ANR
DetailsTroy Cobbley
I tested all of the fire sprinkler device interconnections with the fire alarm system. I also verified most corrections previously noted by Forrest. The smoke detector for door release located on the first floor is still an issue.
INSP-Final Inspection7/13/20127/13/20127/13/2012PCANC
DetailsTroy Cobbley
Overbooked due to inspection load. Contractor notified. I spoke to the installing electrician and deferred him to Romeo Gervais about the horn heights and the problem with placing the smoke detecotrs for door release within 5' and center of the doors. Romeo later called me back and stated that he is ok with the horn height as long as the required sound level is met but the smoke detectors for door release will need to meet code or an alternative will need to be proposed that meets the intent of the code. I also spoke to Jason with AEI about these issues.
INSP-Final Inspection7/11/20127/12/20127/12/2012PFAIL
DetailsForrest France
Items noted during initial acceptance test include; horn only appliances throughout all units on all floors do not meet mounting heights per NFPA 72, need to relocate SD at the 1st and 2nd floor north elevator lobbies, relocate one SD for door hold release at the 1st floor, provide A/V at the1st floor laundry room per plan, repair one WP A/V at the parking garage, post signage at the doors to the FACP room, cd settings at five locations adjusted while on site. Items tested okay include all five ID detectors for damper shutdown, MP at the panel, and notification testing on all floors. Sprinkler monitoring, elevator recall, NAC's, EOL's and panel items not tested.
FIR-Aging Inspection5/1/20125/1/20125/1/2012 DONE
DetailsForrest France
Work in progress, construction underway.