INSP-Final Inspection | 12/14/2011 | 12/15/2011 | 12/16/2011 | A | PASS |
Forrest France
|
|
|
Verified completed adjustments. Fire sprinkler permit finaled.
|
INSP-Final Inspection | 11/18/2011 | 11/21/2011 | 11/21/2011 | A | PEND |
Forrest France
|
|
|
Scope of work is complete. Final pending adjustments to coverage at two locations. Unistrut installed adjacent to pendent heads obstructs pattern development.
|
INSP-Sprinkler Rough-in | 9/28/2011 | 9/29/2011 | 9/30/2011 | P | PART |
Forrest France
|
|
|
Overhead fire sprinkler work approved for cover. Upright head separation and one missing pendent head to be verified at final.
|
INSP-Sprinkler Rough-in/Hydro | 9/23/2011 | 9/27/2011 | 9/28/2011 | P | NR |
Forrest France
|
|
|
Plans are not consistent with the field installation.
|