Permit Information
Permit NumberFIR11-00477
StatusFinaled
Name ALLIED GENERAL FIRE & SECURITY
Site Address 650 N ARMSTRONG PL
Project NameWinco Foods Records Retention
Customer Number 
ePlanReviewNo
Description
This fire alarm permit is to provide sprinkler monitoring and HVAC monitoring/shutdown for a new building. The new devices will be tied in to an existing fire alarm panel located in the main building. This permit scope includes a pull station, monitor modules, relays, and duct detectors

Associated building permit: BLD11-00781 Winco General Office - Records Storage Building - To construct a new 9,365 square foot, one story, masonry and steel framed record storage building and related site improvements. This building is being built on the north side of the existing Winco office building. This building is being structurally designed for a future second floor addition for storage. This building is fully fire sprinkled. All construction per the approved plans and attached comment list. JCM
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/17/201110/18/201110/18/2011PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Sprinkler Rough-in/Hydro10/17/201110/18/201110/17/2011PCANC
DetailsTroy Cobbley
please contact Jeremy at ###-#### Phone #: ###-#### >> Inspection requested via web by David Dilley Inspection cancelled from web by: David Dilley
INSP-Final Inspection10/6/201110/7/201110/7/2011ACANC
DetailsTroy Cobbley
Cancel per Jeremy at ###-####
INSP-Final Inspection9/16/20119/19/20119/19/2011AFAIL
DetailsTroy Cobbley
All items tested ok except the interconnection of wires run between the buildings. The circuits were not installed in metalic conduit as per the redlined plans, but instead in PVC. After confiring with Doug Poedy it was clear in both NFPA 72 and NEC that the only options for the interbuilding fire alarm circuiting are: provide a metalic cable shield (grounded to the building electrode system), run in metalic conduit (grounded to the building electrode system), or provide isolation modules. Items also needing addressed are the descriptions for the HVAC units in the records storage building.
INSP-Final Inspection9/15/20119/16/20119/16/2011PCANC
DetailsTroy Cobbley
Please contact Jeremy at ###-#### Phone #: ###-#### >> Inspection requested via web by David Dilley Inspection cancelled from web by: David Dilley