Permit Number | FIR11-00482 |
Status | Finaled |
Name |
SIMPLEX GRINNELL
|
Site Address |
10792 W FRANKLIN RD
|
Project Name | IDAHO POWER OPERATIONS CENTER |
Customer Number | |
ePlanReview | No |
Description |
This quick permit scope is to relocate three existing door holders and corresponding smoke detectors, delete two wall-mount horn/strobes, and provide three new ceiling mount horn/strobes. The new devices are to be tied in to the existing system. Approval is subject to field measurement of the EOL voltage drop. For appliances with an operating voltage range of 16V – 33V, the minimum acceptable voltage is 19.6V with the AC power off. Any measurement below this voltage will be considered insufficient to run the NACs at the end of useful battery life of 20.4V. UL 864, Standard for Control Units for Fire Signaling Systems. The installing contractor shall have available at final inspection a voltage meter and measure end of line voltages; witnessed by the field inspector. There are no written review comments. Associated building permit: BLD11-01371 (IDAHO POWER OPERATIONS CENTER – Vestibule and Conference room remodel) Permit is to remodel an existing conference room and an existing entry vestibule. This building is not fire sprinklered. Approval contingent upon adhering to the approved plans on file and plan review report. Work to include: construction of new interior non-bearing wall to create alcoves for existing doors and to define new vestibule, installation of new doors / accessible hardware, and finishes in compliance with chapter 8 of the 2009 IBC. This building is not Fire Sprinklered. **TLW**
|