INSP-Final Inspection | 9/28/2011 | 9/29/2011 | 9/29/2011 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled. The bulbs and the wiring have been removed from the lights under the hood.
|
INSP-Final Inspection | 9/26/2011 | 9/27/2011 | 9/27/2011 | A | FAIL |
Troy Cobbley
|
|
|
Everything functioned except the lights under the hood did not shut off when the system activated.
|
INSP-Supply line flush | 9/19/2011 | 9/20/2011 | 9/20/2011 | P | FAIL |
Troy Cobbley
|
|
|
The manual pull station is mounted too high, Also after a discussion it was fount that the exhaust fan does not stay on and the makeup air shut off when the the system activates. The lights under the hood also need to be verified that they shut off when the suppression system activates. No inspection was actually done.
|