INSP-Final Inspection | 10/24/2012 | 10/24/2012 | 10/30/2012 | P | PASS |
Forrest France
|
|
|
Corrections finished. Fire sprinkler permit finaled.
|
INSP-Final Inspection | 10/22/2012 | 10/22/2012 | 10/30/2012 | P | PART |
Forrest France
|
|
|
Plan modifications and field install checked for equivalence.
|
INSP-Final Inspection | 10/17/2012 | 10/19/2012 | 10/30/2012 | A | PART |
Forrest France
|
|
|
Field verified corrections.
|
FIR-Aging Inspection | 7/3/2012 | 7/3/2012 | 7/3/2012 | | DONE |
Forrest France
|
|
|
|
INSP-Sprinkler Rough-in | 4/2/2012 | 4/3/2012 | 4/4/2012 | P | PART |
Forrest France
|
|
|
Previous C/N items verified for completion. Finished walkthrough for coverage adjustments at the overhead AMH tracks and cubbies. Noted missing coverage at the SW corner of the north half photo bay. Plan modifications pending.
|
INSP-Sprinkler Rough-in/Hydro | 3/28/2012 | 3/29/2012 | 3/30/2012 | A | PART |
Forrest France
|
|
|
System 4 overhead hydrostatic test passed. Completed re-inspection for relocated and added pendent heads at the AMH track areas. Noted missing hangers on three new arm-overs >2'.
|
INSP-Sprinkler Rough-in/Hydro | 2/28/2012 | 3/1/2012 | 3/2/2012 | P | PART |
Forrest France
|
|
|
Re-inspection for noted correction items at system 4 photo bay and link include: retainers at mains and branchlines secured; adjustments in pendent head locations at AMH track underway- overhead storage cubbies may also present obstruction issues when installed; seismic bracing completed; pendent heads at the link drop ceiling are matched with grid install to date. Plans will need revised to reflect field modifications at several areas.
|
INSP-Sprinkler Rough-in/Hydro | 1/12/2012 | 1/13/2012 | 1/13/2012 | P | FAIL |
Forrest France
|
|
|
Rough-in inspection completed for system # 4 clean link and photo bay. Noted items include missing retainers at several beam clamps on branchlines, 4" and 6" mains, missing hanger at arm-over, pendent heads are blocked or obstructed at numerous locations due to proximity to AMH brackets, flex head whips are not yet installed at various areas in the clean link, missing seismic bracing at the 6" main, secure EQ brace at the 4" main, added 90s at branchlines in the photo bay are not included in the calcs.- branch line restraint at these locations shall be provided per NFPA 13 9.3.6.4.
|
INSP-Conference | 2/1/2012 | 2/3/2012 | | A | |
Forrest France
|
|
|
Phone #: ###-#### >> Inspection requested via web by Alicia Pauley
|