Permit NumberFIR11-00528
StatusFinaled
Name ALLIED GENERAL FIRE & SECURITY
Site Address 1256 E EXCHANGE ST
Project NameUBIQUITEL MSC
Customer Number 
ePlanReviewNo
Description
10-20-11 PLAN MODIFICATION (no initiating devices affected): This plan modification is to consolidate the two existing fire alarm panels into one. The addressable panel as the remaining panel and the conventional panel is being removed. An addressable module is being provided so the system can monitor an existing conventional device. In addition, an AES RF radio with an IntelliTap is being provided to replace the existing DACT.

10-4-11:This fire alarm permit is to remove three fire suppression control panels and associated equipment for the existing clean agent suppression systems. The existing dry preaction system devices are also being removed. The master panel used for the sprinkler system monitoring and the slave panel used for the manual fire alarm system are to remain. There is no associated building permit.
Fire Alarm System background: There was originally an existing sprinkler monitoring only panel (Notifier SFP-10UD) that provided zones for a water flow switch, a pull station, and a tamper switch. Then, under FIR00-00468, an additional “slave” panel was provided to accommodate a manual fire alarm system with full notification, as well as connections to monitor alarm, trouble, and supervisory signals for suppression panels used to release two FM200 systems and a dry preaction system. This configuration and installation was approved under the 1997 UFC.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection11/30/201111/30/201111/30/2011PPASS
DetailsForrest France
Scope of fire alarm permit work finaled. *Note: defficient items including missing smoke detection at leibert units, location of existing notification appliances and items 1 and 2 on the plan review are to remain at this time per building official J. Blais and fire chief R. Gervais.

*The existing switch gear room has been vacated and all electrical equipment and stationary storage batteries have been removed by the tenant. The clean agent fire protection and detection system has been removed under FIR11-00528. The existing fire/smoke rated wall assembly seperating the switch gear room and the mechanical room is no longer required and has been modified and subsequently no longer maintains an approved 1 hour rated assembly. The opening protection seperating the switch gear room and the mechanical room, (smoke dampers), may have been impaired due the removal of the area smoke detection required as part of the clean agent system removal. The mechanical division, building official, and fire code official have approved the 3 air handling units to remain as is, under the condition the space served by the air handling units remains unoccupied. An occupancy permit shall be obtained prior to untilization of the vacated space. *SJA*
INSP-Conference11/28/201111/28/201111/28/2011PDONE
DetailsForrest France
INSP-Conference11/23/201111/23/201111/23/2011ADONE
DetailsForrest France
On site meeting with contractor and mechanical inspectors regarding missing smoke detection at existing air handler units and conditions per IMC 2009 sec. 606.
INSP-Conference11/21/201111/21/201111/21/2011PDONE
DetailsForrest France
Conversations with general and sub contractors regarding noted correction items.
INSP-Final Inspection11/14/201111/15/201111/15/2011AFAIL
DetailsForrest France
See plan annotations for noted items including notification appliance coverage and location issues, missing SD at the three liebert units, batteries at the FACP, etc.
INSP-Final Inspection11/11/201111/14/201111/14/2011PCANC
DetailsForrest France
Call Randy Phone #: ###-#### >> Inspection requested via web by Mike Brown Inspection cancelled from web by: Mike Brown
INSP-Final Inspection11/9/201111/10/201111/10/2011PFAIL
DetailsTroy Cobbley
Arrived at the job site but Randy called me to let me know there would be no access due to the property manager being in Gerome. No inspection was performed.
INSP-Alarm Testing10/7/201110/10/201110/10/2011PCANC
DetailsTroy Cobbley
Per Jason this project is not quite ready for a final inspection. It will be rescheduled.
INSP-Alarm Testing10/7/201110/10/201110/7/2011PCANC
DetailsForrest France
The phone number is Dave Dilley. Phone #: ###-#### >> Inspection requested via web by Mike Brown Inspection cancelled from web by: Mike Brown